ON / OFF

11. SETUP AT LOCAL SITE AND OTHERS

11-1. Indoor Unit

11-1-1. Test Run Setup on Remote Controller

<Wired remote controller>

1. When pushing TEST button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. Then push ON / OFF button.

“TEST” is displayed on LC display during operation of Test Run.

During Test Run, temperature cannot be adjusted but air volume can be selected.

In heating and cooling operation, a command to fix the Test Run frequency is output.

Detection of error is performed as usual. However, do not use this function except case of Test Run be- cause it applies load on the unit.

2.Use either heating or cooling operation mode for [TEST].

NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after operation has stopped.

3.After a Test Run has finished, push TEST button again and check that [TEST] on LC display has gone off. (To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote controller.)

<Wireless remote controller>

(4-way Air Discharge Cassette Type only)

1 Turn off power of the unit.

Remove the adjuster attached with sensors from the ceiling panel. For removing, refer to the Installation manual attached to the ceiling panel.

(Be careful to handle the adjuster because cables are connected to the sensor.)

Remove the sensor cover from the adjuster. (1 screw)

2 Change ON of Bit [1: TEST] of the sensor P.C. board switch [S003] to OFF.

Mount the sensor cover and mount the adjuster with sensor to the ceiling panel.

Turn on power of the unit.

3

4

5

Push

button on the wireless remote controller and select [COOL] or [HEAT] operation

mode using

MODE button.

(All the display lamps of sensors on the wireless remote controller flash during Test Run.)

Do not perform Test Run operation in other modes than [HEAT] / [COOL] mode.

Detection of error is performed as usual.

After Test Run operation, push ON / OFF button to stop the operation.

Turn off power of the unit.

Return Bit [1] of the sensor P.C. board switch [S003] to the original position. (ON OFF)

Mount the adjuster with sensors to the ceiling panel.

Sensor cover

DIP switch S003 Bit 1: OFF ON

ON

4

3

2

1

Sensor board

Adjust corner cap with sensor

– 105 –

Page 105
Image 105
Toshiba RAV-SP1404ATZ-E, RAV-SM1404UT-E Test Run Setup on Remote Controller, 105, Wired remote controller, Push

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.