No.

Item

 

Outline of specifications

 

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Room temp.

2)

Using the Item code 06, the setup temperature in heating Shift of suction

 

control

 

operation can be corrected.

 

 

 

 

 

 

 

 

temperature in heating

 

(Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

 

Setup data

 

 

 

 

0

 

2

 

4

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp. correction

 

+0°C

 

+2°C

 

+4°C

+6°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Automatic

1)

Based on the difference between Ta and Ts, the operation

 

 

capacity control

 

frequency is instructed to the outdoor unit.

 

 

 

 

(GA control)

2)

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 90 seconds, the room temperature difference

 

 

 

 

 

 

 

 

between temperature detected by Ta and Ts and the

 

 

 

 

varied room temperature value are calculated to obtain

 

 

 

 

the correction value of the frequency command and then

 

 

 

 

the present frequency command is corrected.

 

 

 

 

 

 

Ta (n) – Ts (n) : Room temp. difference

 

 

 

 

 

 

 

 

n

: Counts of detection

 

 

 

 

 

 

 

 

Ta (n-1) – Ts (n)

: Varied room temp. value

 

 

 

 

 

 

n – 1

: Counts of detection of 90 seconds before

 

 

 

3)

Heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 1 minute (60 sec.), the room temperature differ-

 

 

 

 

ence between temperature detected by Ta and Ts and the

 

 

 

 

varied room temperature value are calculated to obtain

 

 

 

 

the correction value of the frequency command and then

 

 

 

 

the present frequency command is corrected.

 

 

 

 

 

 

Ts (n) – Ta (n)

: Room temp. difference

 

 

 

 

 

 

 

 

n

: Counts of detection

 

 

 

 

 

 

 

 

Ta (n) – Ta (n – 1): Varied room temp. value

 

 

 

 

 

 

n – 1

: Counts of detection of 1 minute before

 

 

 

4)

Dry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The frequency correction control is same as those of the

 

 

 

 

cooling operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

However the maximum frequency is limited to approxi-

 

 

 

 

mately “S6”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note) When LOW is set up, the maximum frequency is

 

 

 

 

limited to approximately “SB”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Automatic

1)

The judgment of selecting COOL/HEAT is carried out as

 

 

cooling/heating

 

shown below. When +1.5 exceeds against Tsh 10 minutes

Tsc: Setup temp. in

 

control

 

and after thermo.-OFF, heating operation (Thermo. OFF)

 

 

cooling operation

 

 

 

exchanges to cooling operation. Description in the

 

 

 

Tsh: Setup temp. in

 

 

 

parentheses shows an example of cooling ON/OFF.

 

 

 

heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ta

 

Cooling

 

 

 

 

 

 

 

 

+ temp. correction of

 

 

 

(˚C)

 

 

 

 

 

 

 

 

 

 

 

 

 

room temp. control

 

 

 

+1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Cooling ON)

 

 

 

 

 

 

or Tsc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tsh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-1.5

 

 

 

(Cooling OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When –1.5 lowers against Tsc 10 minutes and after thermo. OFF, cooling operation (Thermo. OFF) exchanges to heating operation.

2)For the automatic capacity control after judgment of cooling/heating, see Item 4.

3)For temperature correction of room temp. control in automatic heating, see Item 3.

– 47 –

Page 47
Image 47
Toshiba RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1404ATZG-E, RAV-SP1404AT-E, RAV-SM804UT-E Setup data

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.