Toshiba RAV-SM804UT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E, RAV-SP1404ATZG-E service manual

Models: RAV-SP1104ATZG-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SM804UT-E RAV-SP1404AT-E RAV-SP1404ATZG-E RAV-SP1104AT-E RAV-SM1104UT-E RAV-SM1404UT-E

1 162
Download 162 pages 56.34 Kb
Page 104
Image 104
Manual background

10-2. Outdoor Unit

1. Setting the jumper wires and DIP switches

Part name

Function

Setting

 

 

 

 

 

J800 to J803

Model switching

Cut these jumper wires according to the following table.

Jumper wire

 

 

 

J804 to J810

Settings

Set these jumper wires to the settings of the P.C. board before

 

 

replacement.

 

 

 

 

 

 

 

 

SW802

Settings

Set SW802 to the setting of the P.C. board before replacement.

 

 

 

 

DIP switch

SW803

LED indication switching

Set SW803 to all OFF.

 

 

 

 

 

SW804

Special operations for service

Set SW804 to all OFF.

 

 

 

 

Model switching (J800 to J803)

Since this service P.C. board is available for several models, cut the jumper wires according to the following table.

If they are not cut correctly, an error code “L10” or “L29” appears on the remote controller and the operation of the air conditioner is disabled.

 

Model name

J 800

J 801

J 802

J 803

 

 

 

 

 

Factory setting (default)

¡

¡

¡

¡

 

 

 

 

 

 

 

RAV-SP1104AT-E

×

¡

¡

¡

 

RAV-SP1404AT-E

¡

×

¡

¡

: Characters that indicate the following:

¡: Connected, × : Cut

No character

...... Standard models

Z

For salt-affected areas

ZG

For heavily salt-affected areas

 

 

 

 

 

 

 

 

 

 

J800 to J803

2.Installing the P.C. board

1)Apply thermal grease to the back (heat sink contacting side) of devices Q200, Q650, DB01, and DB02. ( Q300 and Q400 are not necessary to be applied thermal grease.)

2)Reuse the insulating sheet. When a small amount of thermal grease is applied to the back of the insulating sheet, it adheres temporarily to the heat sink, which makes it easy to attach the insulating sheet.

3)Insert the P.C. board, align the holes of the insulating sheets, semiconductor devices, and heat sinks, and then secure them with screws.

4)Connect the lead wires according to the wiring diagram sticked on the backside of the pannel .

Apply thermal grease to

the back (heat sink contacting side) of Q200, Q650, DB01, and DB02.

Reuse the insulating sheet. Applying thermal grease to the back of the insulating sheet makes it easy to attach the insulating sheet.

– 104 –

Page 104
Image 104