DN

Item

 

 

Contents

At shipment from factory

 

 

 

 

 

 

 

 

0000: None

 

0000: 0.5 h to 0.012: 0 h

 

42

Self-clean operation time

Set when compressor-ON time is 10 to 60 minutes.

0002: 1 hour

When ON-time is 60 minutes or more,

 

 

 

 

 

the double of this operation time setting is set.

 

 

 

 

 

 

45

Selection of louver horizontal discharge

0000: Smudging-less setting

 

0000: Smudging-

position

0002: Cold draft preventive setting

 

less setting

 

 

 

 

 

 

 

 

C2

Current demand X% to outdoor unit

0050: 50%

to

0100: 100%

0075: 75%

 

 

 

 

 

 

 

 

0000: No

 

 

 

 

 

Clean operation is performed in case of stop by HA input.

 

 

 

HA operation output OFF during clean operation in case of

 

 

 

 

stop by remote controller

 

 

CC

Setting of self-clean operation forced stop

 

 

 

 

0000: None

 

 

0001: Yes

 

 

 

 

 

Clean operation is not performed in case of stop by HA input.

 

 

 

HA operation output ON during clean operation in case of stop

 

 

 

 

by remote controller

 

 

 

 

 

 

 

 

 

The air conditioner stops (including fire alarm such as remote

 

 

 

monitor system) while setup of [ON/OFF] operation prohibited

 

CD

Clean operation stop function when

(Central 1, 2) is performed from the central controller side.

0000: Valid

[ON/OFF] operation is prohibited.

0000: Valid (Clean operation)

 

 

 

 

 

 

 

 

 

 

0001: Invalid (No clean operation)

 

 

 

 

 

 

 

D0

Existence of remote controller save function

0000: Invalid (Impossible)

0001: Valid (Possible)

0001: Valid (Possible)

 

 

 

 

 

D1

Existence of 8°C heating operation function

0000: Invalid (Impossible)

0001: Valid (Possible)

0001: Invalid (Impossible)

 

 

 

 

D3

Revolution frequency of self clean operation

0000: Invalid (Self clean operation is not carried out.)

0001: Valid

0001: Valid (Self clean operation is practiced with 210 rpm.)

(210 rpm / operation)

 

 

 

 

 

 

 

 

 

D4

Display / No display of

0000: Display

 

0001: No display

0000: Display

[Dry operation] during self clean operation

 

 

 

 

 

 

 

 

 

 

 

 

F0

Louver swing mode

0000: No synchronization

0001: 4-way synchronization

0001: 4-way

0002: Dual

 

0003: Cycle

synchronization

 

 

 

 

 

 

 

 

 

 

 

0000: Release (Free)

 

 

 

F1

Louver No.1 fixed position

0001 to 0005: Horizontal discharge position to

0000: Release

 

 

 

Downward discharge position

 

 

 

 

 

 

 

 

 

0000: Release (Free)

 

 

 

F2

Louver No.2 fixed position

0001 to 0005: Horizontal discharge position to

0000: Release

 

 

 

Downward discharge position

 

 

 

 

 

 

 

 

 

0000: Release (Free)

 

 

 

F3

Louver No.3 fixed position

0001 to 0005: Horizontal discharge position to

0000: Release

 

 

 

Downward discharge position

 

 

 

 

 

 

 

 

 

0000: Release (Free)

 

 

 

F4

Louver No.4 fixed position

0001 to 0005: Horizontal discharge position to

0000: Release

 

 

 

Downward discharge position

 

 

 

 

 

 

 

 

The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).

– 111 –

Page 111
Image 111
Toshiba RAV-SP1404ATZG-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E, RAV-SP1404AT-E, RAV-SM804UT-E, RAV-SP1404ATZ-E 111

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.