11-4. Outdoor Unit

11-4-1. Refrigerant Recovery Control

The “ozone destruction coefficient” of HFC refrigerant is 0 and the discharge regulation is set as anathermal effect gas.

To this model, a switch which can perform the refrigerant recovery (pump down) by the outdoor unit is mounted so that it is easy to react against the environment at reinstalling or rejection time.

[Operation method]

1)Set the mode of the indoor unit to fan mode.

2)Set all DIP switch SW804 to OFF (Initial status) and then push the button switch SW801 for approx. 1 second. The cooling operation starts. (During this time, D805 (Green LED) flashes.)

This operation finishes by 10 minutes.

3)After operation for 3 minutes or more, close valve at liquid side.

4)After recovery of refrigerant, close valve at gas side.

5)Push the button switch SW801 again for approx. 1 second. The outdoor unit stops.

6)Stop the indoor unit and then turn off the power supply.

W804: All OFF (As initial status)

SW801: Push for 1 second.

 

4

ON

 

3

 

2

 

 

1

The D805 (Green LED) flashes.

D800

 

 

 

 

 

 

D801

 

 

 

 

 

 

D802

 

 

 

 

 

 

D803

 

 

 

 

 

 

D804

 

 

 

 

 

4

D805

 

 

 

ON

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

4

 

 

 

 

 

3

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

11-4-2. Various setting on outdoor unit (Existing piping, Power save, Cooling-only, etc.)

The following settings are available by DIP switch setup and jumper line setup.

Function

 

 

 

 

Set position

 

 

Control contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when mounting a duct to the discharge

 

 

 

 

 

 

port of the outdoor unit. Add 3 taps to the upper limit value of the

High static

 

 

 

 

 

outdoor fan tap.

 

 

 

 

 

 

 

 

 

pressure setup

 

 

 

 

 

The operation is performed with

 

 

 

 

 

 

 

 

 

 

 

 

(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).

 

 

 

 

SW802

 

In this case, the outdoor noise level may increase.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing piping

 

 

 

 

High static pressure setup

Turn the switch to ON when Ø19.1 is used for the existing pipe.

 

 

 

 

 

 

 

 

 

 

 

4

In this case, the heating capacity may lower according to outside

 

 

 

setup

 

 

 

 

Existing piping setup

 

 

 

3

temp. and indoor temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Power save setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when using the power save function.

Power save setup

 

ON

 

 

Snow-proof fan control

 

 

1

The control to lower the compressor frequency (Approx. –10%) is

 

 

 

 

 

performed by indoor heat exchanger temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When snow enters from clearance of the fan guard or heat

Snow-proof fan

 

 

all are OFF at shipment.

exchanger into blast path and it is accumulated, the control to

 

 

prevent generation of motor lock is validated.

 

 

 

 

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When outside temp. is below 0°C though the compressor stops,

 

 

 

 

 

 

 

 

 

 

 

 

the outdoor fan operates with W5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost time

 

 

 

 

J805, J806

The defrost interval is cut to shorten it than the standard status.

 

 

 

 

For contents of control and cutting method, refer to

 

 

change

 

 

 

 

 

 

 

 

 

 

 

 

Section 8-2-10. Defrost control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When it is needed to lower the maximum value of the

 

 

 

 

 

 

 

 

compressor frequency, cut the jumper line.

 

 

 

 

 

 

 

 

 

 

Max. frequency at cooling/heating is lowered.

 

 

 

 

 

 

 

 

 

 

In this case the Max. capacity decreases.

 

 

 

 

Max. frequency

 

 

 

 

 

 

Max. frequency of compressor

 

 

 

 

 

 

 

 

 

 

J807

 

 

 

 

 

 

 

 

 

 

 

change

 

 

 

 

 

 

 

RAV-SP1104

 

RAV-SP1404

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

HEAT

 

COOL

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard status

 

53.4

 

71.4

 

64.2

 

90.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When J807 is cut

 

53.4

 

64.2

 

64.2

 

72.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling-only setup

 

 

 

 

J808

When using the air conditioner as a cooling-only conditioner, cut

 

 

 

 

the jumper line.(An air conditioner can be changed to cooling-

 

 

 

 

 

 

only conditioner by “0F” of DN code on the remote controller.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 122 –

Page 122
Image 122
Toshiba RAV-SM804UT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E Operation method, Refrigerant Recovery Control, 122

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.