– 72 –

Check Code List (Outdoor)

¡ : Go on, ¥ : Flash, l : Go off ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED

Remote

Sensor lamp part

 

 

 

 

 

 

Automatic

Operation

controller

Block indication

 

Representative defective position

 

Detection

Explanation of error contents

 

 

reset

continuation

indication

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

 

Flash

 

 

 

 

 

 

 

F04

¥

¥

¡

 

ALT

Outdoor unit Discharge temp. sensor (TD) error

 

Outdoor

Open/Short of discharge temp. sensor was detected.

×

×

F06

¥

¥

¡

 

ALT

Outdoor unit Temp. sensor (TE, TS, TL) error

 

Outdoor

Open/Short of heat exchanger temp. sensor was detected.

×

×

 

 

Miswiring between TE sensor and TS sensor

F08

¥

¥

¡

 

ALT

Outdoor unit Outside temp. sensor (TO) error

 

Outdoor

Open/Short of outside temp. sensor was detected.

¡

¡

F07

¥

¥

¡

 

ALT

Outdoor unit Temp. sensor (TL) error

 

Outdoor

Open/Short of heat exchanger temp. sensor was detected.

×

×

F12

¥

¥

¡

 

ALT

Outdoor unit Temp. sensor (TS) error

 

Outdoor

Open/Short of suction temp. sensor was detected.

×

×

F13

¥

¥

¡

 

ALT

Outdoor unit Temp. sensor (TH) error

 

Outdoor

Open/Short of heat sink temp. sensor (Board installed) was detected.

×

×

F15

¥

¥

¡

 

ALT

Outdoor unit Misconnection of temp. sensor (TE, TS)

Outdoor

Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected.

×

×

F31

¥

¥

¡

 

SIM

Outdoor unit EEPROM error

 

Outdoor

Outdoor P.C. board part (EEPROM) error was detected.

×

×

H01

l

¥

l

 

 

Outdoor unit Compressor break down

 

Outdoor

When reached min-Hz by current release control, short-circuited current (Idc) after

×

×

 

 

 

 

DC excitation was detected.

H02

l

¥

l

 

 

Outdoor unit Compressor lock

 

Outdoor

Compressor lock was detected.

×

×

H03

l

¥

l

 

 

Outdoor unit

Current detection circuit error

 

Outdoor

Current detection circuit error

×

×

H04

l

¥

l

 

 

Outdoor unit Case thermostat operation

 

Outdoor

Case thermostat operation was detected.

×

×

L10

¥

¡

¥

 

SIM

Outdoor unit

Setting error of service P.C. board type

Outdoor

When outdoor service P.C. board was used, model type select jumper setting was inappropriate.

×

×

 

 

 

 

 

 

 

 

 

 

1) Defective parts on outdoor P.C. board (MCU communication, EEPROM, TH sensor error)

×

×

L29

¥

¡

¥

 

SIM

Outdoor unit

Other outdoor unit error

 

Outdoor

2) When outdoor service P.C. board was used, model type selection was inappropriate.

 

 

 

 

 

 

 

 

 

 

3) Other error (Heat sink abnormal overheat, gas leak, 4-way valve inverse error) was detected.

 

 

P03

¥

l

¥

 

ALT

Outdoor unit

Discharge temp. error

 

Outdoor

Error was detected by discharge temp. release control.

×

×

P04

¥

l

¥

 

ALT

Outdoor unit

 

 

Outdoor

When case thermostat worked, error was detected by high release control from indoor/

×

×

 

High pressure system error, Power supply voltage error

outdoor heat exchanger temp. sensor. Power supply voltage error

P05

¥

l

¥

 

ALT

Power supply error

 

Outdoor

Power supply voltage error

×

×

P07

¥

l

¥

 

ALT

Outdoor unit Heat sink overheat

 

Outdoor

Abnormal overheat was detected by outdoor heat sink temp. sensor.

×

×

P15

¥

l

¥

 

ALT

Gas leak detection

 

Outdoor

Abnormal overheat of discharge temp. or suction temp. was detected.

×

×

P20

¥

l

¥

 

ALT

Outdoor unit

High pressure system error

 

Outdoor

Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor.

×

×

P22

¥

l

¥

 

ALT

Outdoor unit

Outdoor fan error

 

Outdoor

Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.

×

×

P26

¥

l

¥

 

ALT

Outdoor unit

Inverter Idc operation

 

Outdoor

Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked.

×

×

P29

¥

l

¥

 

ALT

Outdoor unit

Position detection error

 

Outdoor

Position detection error of compressor motor was detected.

×

×

E01

¥

l

l

 

 

No remote controller master unit

 

Remote

Signal was not received from indoor unit.

 

 

Remote controller communication error

 

controller

Main remote controller was not set. (including 2 remote controllers)

 

 

 

 

 

 

 

 

 

E02

¥

l

l

 

 

Remote controller send error

 

Remote

Signal cannot be sent to indoor unit.

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

E03

¥

l

l

 

 

Regular communication error between indoor and

 

Indoor

No communication from remote controller and network adapter

¡

×

 

 

remote controller

 

E04

l

l

¥

 

 

Indoor/Outdoor serial error

 

Indoor

Serial communication error between indoor and outdoor

¡

×

E08

¥

l

l

 

 

Duplicated indoor addresses

²

Indoor

Same address as yours was detected.

¡

 

E09

¥

l

l

 

 

Duplicated main remote controllers

 

Remote

In 2-remote controller control, both were set as master.

×

×

 

 

 

controller

(Indoor master unit stops warning and follower unit continues operation.)

E10

¥

l

l

 

 

Communication error between CPU

 

Indoor

MCU communication error between main motor and micro computer

¡

 

E18

¥

l

l

 

 

Regular communication error between master and

 

Indoor

Regular communication was impossible between master and follower indoor units.

¡

×

 

 

follower indoor units

 

Communication between twin master (Main unit) and follower (sub unit) was impossible.

L03

¥

l

¥

 

SIM

Duplicated indoor master units

²

Indoor

There are multiple master units in a group.

×

×

L07

¥

l

¥

 

SIM

There is group cable in individual indoor unit.

²

Indoor

When even one group connection indoor unit exists in individual indoor unit

×

×

L08

¥

l

¥

 

SIM

Unset indoor group address

²

Indoor

Indoor address group was unset.

×

×

L09

¥

l

¥

 

SIM

Unset indoor capacity

 

Indoor

Capacity of indoor unit was unset.

×

×

L30

¥

¡

¥

 

SIM

Outside error input to indoor unit (Interlock)

 

Indoor

Abnormal stop by CN80 outside error input

×

×

P19

¥

l

¥

 

ALT

4-way valve inverse error

 

Indoor

In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up ofTE, TS.

¡

×

 

 

Outdoor

²When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.

Page 72
Image 72
Toshiba RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E, RAV-SP1404ATZG-E Check Code List Outdoor, Way valve inverse error

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.