Toshiba RAV-SP1404ATZG-E, RAV-SM1404UT-E 57, Item, Outline of specifications, Remarks

Models: RAV-SP1104ATZG-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SM804UT-E RAV-SP1404AT-E RAV-SP1404ATZG-E RAV-SP1104AT-E RAV-SM1104UT-E RAV-SM1404UT-E

1 162
Download 162 pages 56.34 Kb
Page 57
Image 57
– 57 –

No.

Item

 

 

Outline of specifications

Remarks

 

 

 

 

 

22

8°C heating/

1)

This functional is intended for the cold latitudes and performs

 

 

Frost protective

 

objective heating operation (8°C heating operation).

 

 

operation

2)

This function is valid only for combination with the outdoor

In a group connection,

 

 

 

 

 

units (Super Digital Inverter (SDI) 4-series outdoor units).

if there is even one

 

 

3)

Using the indoor DN code [D1] (1 bit), Valid/Invalid of this

combination with other

 

 

unit, “This function is not

 

 

 

function is set up at the customer’s side.

 

 

 

provided.” is displayed.

 

 

 

The setup by DN code is Invalid [0]/Valid [1] and Invalid [0]

 

 

 

 

 

 

 

has been set at the shipment.

 

 

 

4)

This operation is the heating operation which sets +8°C as

 

 

 

 

the setup temperature of the target.

 

 

 

5)

This function starts operation by pushing temperature

The setup temperature

 

 

 

button

during heating operation; besides by pushing

jumps from [18] to [8].

 

 

 

button for 4 seconds or more after temperature

 

 

 

 

reached the minimum set temperature.

 

 

 

6)

To stop/release this operation, select and execute one from

 

 

 

 

the following operations.

 

 

 

 

Push

button: Heating operation (18°C setting)

 

 

 

 

continues.

 

Push [START/STOP] button: Air conditioner stops.

(Heating 18°C operation at the next start)

MODE

ƒPush Manual background : Other operation mode is selected and the operation continues.

7)As the setup temperature is +8°C and the human heating is not targeted, the cold air discharge preventive control (Item 7) is made invalid to suppress the intermittent operation.

8)The settings of the air direction and air volume are changeable during this operation.

9)The indoor fan stops to protect the compressor for

2 minutes after start of heating operation (Thermo-ON) by this function.

– 57 –