Toshiba RAV-SM1404UT-E, RAV-SM1104UT-E 144, Detachment, Attachment, No. Part name, Procedure

Models: RAV-SP1104ATZG-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SM804UT-E RAV-SP1404AT-E RAV-SP1404ATZG-E RAV-SP1104AT-E RAV-SM1104UT-E RAV-SM1404UT-E

1 162
Download 162 pages 56.34 Kb
Page 144
Image 144
– 144 –

No. Part name

Procedure

Remarks

11 Heat

1. Detachment

exchanger

1) Recover the refrigerant gas.

 

2)Carry out work of item 1 of Š.

3)Remove refrigerant pipe at indoor unit side.

4)Remove the fixing screws and then remove the piping cover. (Ø4 ×10, 3 pcs.)

5)Remove the drain hose from the drain pump and remove the fixing screws to

remove the drain pump stand.

Fixing screws (Ø4 ×10)

(Ø4 ×8, 3 pcs.)

 

6) While pushing the heat exchanger, remove

 

the fixing band, fixing screws and the heat

 

exchanger. (Ø4 ×8, 3 pcs.)

 

 

Piping cover

2. Attachment

 

Fixing screws

1) Mount the heat exchanger with the fixing

(Ø4 ×10)

band and the fixing screws. (Ø4 ×8, 3 pcs.)

 

2) Fix the parts as before in order of drain pump stand piping cover.

3)Connect the refrigerant pipe as before and then apply vacuuming.

4) Following to work of item 2 of Š, attach

Drain pump stand

the parts as before.

 

Fixing screws (Ø4 ×10)

Fixing band

Fixing screw

Fixing band

Heat exchanger

– 144 –

Page 144
Image 144
Toshiba RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E, RAV-SP1404AT-E 144, Detachment, Attachment, No. Part name, Procedure