3. Outdoor fan control

Revolution frequency allocation of fan taps [rpm]

 

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

SP110

Up

200

240

240

260

320

380

480

500

530

610

640

660

720

780

SP140

Down

200

280

360

400

500

520

550

630

660

700

740

820

3-1) Cooling fan control

The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency. The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).

Only for 60 seconds after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TL sensor.

TL [˚C]

 

WE tap

58

 

55

 

 

+1 tap / 20 sec

 

Up to the maximum

 

revolution frequency of each zone

38

Revolution frequency hold

35

–1 tap / 20 sec

 

 

Up to the minimum

 

revolution frequency of each zone

3-2) Heating fan control

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

38°C TO

W6

WC

W8

WC

WA

WD

 

 

 

 

 

 

 

29°C TO < 38°C

W5

WB

W7

WC

W9

WC

 

 

 

 

 

 

 

15°C TO < 29°C

W4

W8

W6

WA

W8

WC

 

 

 

 

 

 

 

5°C TO < 15°C

W3

W6

W5

W8

W7

WA

 

 

 

 

 

 

 

0°C TO < 5°C

W2

W4

W4

W6

W5

W8

 

 

 

 

 

 

 

–4°C TO < 0°C

W2

W3

W3

W5

W4

W6

 

 

 

 

 

 

 

TO < –4°C

W1

W2

W1

W4

W2

W6

 

 

 

 

 

 

 

TO error

W1

WC

W1

WC

W2

WD

 

 

 

 

 

 

 

 

 

 

 

: WB for SP110

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (Control from minimum W1 to maximum (according to the following table))

For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TE sensor.

TE [˚C]

–2 taps / 20 sec. (Up to W1)

Stop timer count

24

–2 taps / 20 sec. (Up to W1)

21

–1 tap / 20 sec. (Up to W1)

18

Revolution frequency hold

15

+1 tap / 20 sec

(Up to the maximum tap of each zone)

ƒWhen TE 24°C continues for 5 minutes, the compressor stops.

It is the same status as the normal thermostat- OFF without error display. The compressor restarts after approx. 2 minutes 30 seconds and this intermittent operation is not abnormal.

In case that the status in item ƒ generates frequently, stain on filter of the suction part of the indoor unit is considered.

Clean the filter and then restart the operation.

Object: SP140

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5°C TO < 10°C

W9

WA

WB

 

 

 

 

–3°C TO < 5°C

WB

WB

WC

 

 

 

 

–10°C TO < –3°C

WC

WC

WC

 

 

 

 

TO < –10°C

WD

WD

WD

 

 

 

 

TO error

WD

WD

WD

 

 

 

 

Object: SP110

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5°C TO < 10°C

W9

WA

WA

 

 

 

 

–3°C TO < 5°C

WA

WA

WB

 

 

 

 

–10°C TO < –3°C

WB

WB

WB

 

 

 

 

TO < –10°C

WD

WD

WD

 

 

 

 

TO error

WD

WD

WD

 

 

 

 

– 62 –

Page 62
Image 62
Toshiba RAV-SP1104ATZG-E, RAV-SM1404UT-E, RAV-SM1104UT-E Outdoor fan control, Cooling fan control, Heating fan control

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.