nConfirmation of indoor unit No. position

nConfirmation of indoor unit No. position

1. To know the indoor unit addresses though position of the indoor unit body is recognized

In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation)

<Procedure>

1

Push

ON / OFF button if the unit stops.

2

Push

UNIT button.

 

Unit No. 1-1is displayed on LCD.

TEMP.

ON / OFF

(It disappears after several seconds.)

The displayed unit No. indicate line address and indoor unit address.

(When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing UNIT button.

 

TIMER SET

FAN

MODE

 

TIME

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

1

Operation

2

<Operation procedure>

1 UNIT button. 2 END

2.To know the position of indoor unit body by address

To confirm the unit No. in the group control

(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)

<Procedure>

The indoor unit numbers in the group control are successively displayed, and fan, louver, and drain pump of the corresponding indoor unit are turned on.

(Follow to the procedure during operation)

1 Push VENT and TEST buttons simultaneously for

4 seconds or more.

Unit No. 1  2 END1 Push VENT and TEST buttons simultaneously for is displayed.

Fans and louvers of all the indoor units in the group control operate.

2 Every pushing UNIT button, the unit numbers in the group control are successively displayed.

The unit No. displayed at the first time indicates the master unit address.

Fan and louver of the selected indoor unit only operate.

3 Push TEST button to finish the procedure.

All the indoor units in the group control stop.

TEMP.

 

 

ON / OFF

1

TIMER SET

FAN

MODE

TIME

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

32

<Operation procedure>

1 4 seconds or more. 2 3 Push TEST button to finish the procedure. 3 END

– 133 –

Page 133