Toshiba RAV-SP1404ATZG-E, RAV-SM1404UT-E 48, Outline of specifications, Remarks, <Cool>

Models: RAV-SP1104ATZG-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SM804UT-E RAV-SP1404AT-E RAV-SP1404ATZG-E RAV-SP1104AT-E RAV-SM1104UT-E RAV-SM1404UT-E

1 162
Download 162 pages 56.34 Kb
Page 48
Image 48
<COOL>

No.

Item

Outline of specifications

Remarks

 

 

 

 

6

Air speed selection

1) Operation with (HH), (H), (L) or [AUTO] mode is carried

HH > H+ > H > L+ >

 

 

out by the command from the remote controller.

L > UL

(2)When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.

<COOL>

Ta (˚C)

 

 

+3.0

 

A

HH

B

+2.5

(HH)

C

 

+2.0

 

H+ (HH)

D

+1.5

H (HH)

 

+1.0

 

L+ (H+)

E

+0.5

L (H)

 

Tsc

 

L (H)

F

–0.5

L (L+)

G

 

Controlling operation in case when thermo of remote controller works is same as a case when thermo of the body works.

If the air speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the air speed changes.

When cooling operation has started, select a downward slope for the air speed, that is, the high position.

If the temperature is just on the difference boundary, the air speed does not change.

Mode in the parentheses indicates one in automatic cooling operation.

<HEAT>

 

 

Ta (˚C)

 

 

(–0.5) –1.0

L (L+)

E

L+ (H)

(0) Tsh

 

H (H+)

 

(+0.5) +1.0

 

 

D

 

H+

 

 

(+1.0) +2.0

(HH)

 

HH

C

(+1.5) +3.0

 

(HH)

B

(+2.0) +4.0

 

A

 

 

Value in the parentheses indicates one when thermostat of the remote controller works.

Value without parentheses indicates one when thermostat of the body works.

If the air speed has been changed once, it is not changed for 1 minute. However when the air speed I exchanged, the air speed changes.

When heating operation has started, select an upward slope for the air speed, that is, the high position.

If the temperature is just on the difference boundary, the air speed does not change.

• Mode in the parentheses indicates one in automatic

Tc: Indoor heat

heating operation.

exchanger sensor

• In Tc 60°C, the air speed increases by 1 step.

temperature

– 48 –

Page 48
Image 48
Toshiba RAV-SP1404ATZG-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E 48, Outline of specifications, Remarks, <Cool>