Toshiba RAV-SM804UT-E, RAV-SM1404UT-E 50, Item, Outline of specifications, Remarks, <Conditions>

Models: RAV-SP1104ATZG-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SM804UT-E RAV-SP1404AT-E RAV-SP1404ATZG-E RAV-SP1104AT-E RAV-SM1104UT-E RAV-SM1404UT-E

1 162
Download 162 pages 56.34 Kb
Page 50
Image 50
<Conditions>

No.

Item

Outline of specifications

Remarks

 

 

 

 

7

Cool air discharge

1) In heating operation, the indoor fan is controlled

In D and E zones, the

 

preventive control

based on the detected temperature of Tc sensor or

priority is given to air

 

 

Tcj sensor. As shown below, the upper limit of the

volume selection setup

 

 

revolution frequency is restricted.

of remote controller.

 

 

However B zone is assumed as C zone for

In A zone while thermo

 

 

6 minutes and after when the compressor

is ON, [PRE-HEAT

 

 

activated.

(Heating ready)] is

 

 

In defrost operation, the control value of Tc is

displayed.

 

 

 

 

 

shifted by 6°C.

 

Tc

(˚C)

 

 

Tcj

 

HH

 

 

32

 

 

H

 

 

30

 

 

L

E zone

 

 

 

28

 

 

UL

D zone

 

26

 

 

 

 

 

20

OFF

C zone

 

 

B zone

 

16

 

 

 

A zone

 

 

 

8 Freeze preventive control

1) The cooling operation (including Dry operation) is

Tcj:

(Low temperature release)

performed as follows based on the detected

Indoor heat exchanger

 

temperature of Tc sensor or Tcj sensor.

 

sensor temperature

 

 

When [J] zone is detected for 6 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone.

In [K] zone, time counting is interrupted and the operation is held.

When [ I ] zone is detected, the timer is cleared and the operation returns to the normal operation.

If the commanded frequency becomes S0 because the operation continues in [J] zone, the return temperature A is raised from 5°C to 12°C until [ I ] zone is detected and the indoor fan operates with [L] mode.

(˚C)

5

I

A

K

2

J

In heating operation, the freeze-preventive control

Tcn:

works if 4-way valve is not exchanged and the

Tc temperature when 5

following conditions are satisfied.

minutes elapsed after

(However the temperature for J zone dashing

activation

control is changed from 2°C to –5°C.)

 

<Conditions>

Tc (n – 1):

Tc temperature at start

• When or is established 5 minutes after

time

activation.

 

Tcn Tc (n – 1) – 5

Tcn < Tc (n – 1) – 1 and Tcn Ta < 5°C

– 50 –

Page 50
Image 50
Toshiba RAV-SM804UT-E, RAV-SM1404UT-E, RAV-SM1104UT-E 50, Item, Outline of specifications, Remarks, <Conditions>