4. Wiring specifications

4. Wiring specifications

Use 2-core with no polar wire.

No. of wires

Size

Match the length of wire to wire length of the central

 

 

 

Up to 1000m: twisted wire 1.25mm2

 

control system.

2

 

Up to 2000m: twisted wire 2.0mm2

 

If mixed in the system, the wire length is

 

 

 

 

 

lengthened with all indoor/outdoor inter-unit wire length at side.

 

To prevent noise trouble, use 2-core shield wire.

Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter

unit setup)

CAUTION

Central control device

1)Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)

2)Apply open process to the last terminal (insulating process).

3)Ground earth wire to 1 point at indoor unit side.

U1

U2

 

 

 

 

 

 

Caution 2

 

 

Outdoor unit

 

 

 

 

 

 

1

2

3

Indoor unit

U3 U4

1

2

3

 

 

 

 

A B

 

Caution 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central control system wiring

 

 

Caution 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

 

1

 

2

 

3

 

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: TCC-LINK adapter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(This option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

 

 

 

 

 

Sub unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub unit

 

 

 

 

 

Master unit

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U3

U4

 

1

 

2

 

3

 

 

 

 

1

 

2

 

3

 

 

 

 

1

 

2

 

3

 

 

 

U3

U4

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

Remote controller

Remote controller

 

Remote controller

 

 

 

(Group operation)

Remote controller

Earth terminal

(Twin operation)

5. P.C. board switch (SW01) setup

When performing collective control by customized setup only, the setup of terminator is necessary.

Using SW01, set up the terminator.

Set up the terminator to only the adapter connected to the indoor unit of least line address No.

Central control device

U1 U2

U3 U4

Central control device

U1 U2

U3 U4

Central control devices: Max. 10 units

Refrigerant line 1

Outdoor unit

Refrigerant line 2

Refrigerant line 3

Refrigerant line 4

1 2 3

Indoor unit U3 U4 Size5. P.C. board switch (SW01) setup 1 2 3

A B

TCC-LINK adapter ( This product ) sold separately

 

1

2

3

1

2

3

 

 

 

Master

 

 

Sub

 

 

 

unit

 

 

unit

U3 U4

1

2

3

1

2

3

 

 

A B

 

A B

 

 

 

 

Remote controller wiring

1 2 3

Indoor/outdoor inter-unit wire (AC230V serial) – 117 – Central control system wiring

* Wiring for No.1 and 2 only

 

 

 

 

 

Sub unit

 

 

 

 

 

 

Master unit

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U3 U4

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

Remote controller

Remote controller

 

Remote controller

Remote controller

Remote controller

 

 

 

 

 

Group operation (Max. 8 units)

Twin operation

Line address

1

2

 

4

 

SW01 Bit 1

ON

OF

 

OF

(OFF at shipment from factory)

SW01 Bit 2

OFF

OFF

 

OFF

(OFF at shipment from factory)

Remarks

Turn SW01 Bit 1 to ON.

As status shipped from factory

 

As status shipped from factory

 

(Reference) Setup contents of switch

 

SW01

Terminator

Remarks

Bit 1

 

Bit 1

 

 

 

OFF

 

OFF

None

Mixed with multi (Link wiring) at shipment from factory

ON

 

OFF

100

Central control by digital inverter only

OFF

 

ON

75

Spare

ON

 

ON

43

Spare

– 117 –

Page 117
Image 117
Toshiba RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104AT-E Wiring specifications, 5. P.C. board switch SW01 setup, 117, Size