42VMC

Installation

E N G L I S H

Drilling the hole in the wall for the connection of the pipes

Ø 80 mm

75 mm

50 mm

The pipes can exit the unit to three different directions (see illustra- tion). For exit to the rear, the wall hole must be made in the position shown in the illustration.

For horizontal installation

To allow the condensate drain pipe to correctly come out of the unit, proceed as follows:

5-10 mm

70 / 80 mm

￿

Ø

￿

 

￿Indoors

￿Outdoors

Drill a 70 or 80 mm diameter hole. The hole must have a 5-10 mm downward slope towards the outside. Insert the plastic conduit provided.

Pass the electrical connecting wires through the conduit (see electrical connections).

Condensate drain pipe

For vertical installation

Connect the PVC pipe to the connection on the drain pan.

ARefrigerant connections

BCondensate drain pipe

A

B

IMPORTANT:

The outdoor unit is designed to operate without the use of condensate water to cool the condenser coil.

It is necessary to discharge the condensate directly into the sewer system, downpipes or to disperse it outside.

Remove from suction grille, the part of grille fixed tonguing, pressing it until tabs is unhooked.

￿

Mount condensate drain pipe cover ￿ supplied, fitting it as necessary.

In the event of condensate discharge pump is used (accessory), the condensate drain pipe can exit together with the refrigerant pipes.

GB - 7

Page 8
Image 8
Carrier 42VMC installation manual For horizontal installation, For vertical installation