INSERT SIDE DRAIN PLUG FOR DOWN DRAIN USE.
DRILL 5/8” DIA. (0.625 mm) HOLE THRU FOR DOWN DRAIN USE.
C10321
Fig. 5 - Condensate Drain Pan
OPTIONAL UNIONS
TO ALLOW FOR CONDENSATE
PAN REMOVAL
4" (102mm)
CONDENSATE
PAN ACCESS
PANEL
C06234
Fig. 6 - External Trap for Condensate Drain
NOTE: Trap should be deep enough to offset maximum unit static difference. A
C06291
Fig. 7 - Condensate Drain Piping Details
Step 6 — Make Electrical Connections
(For more details, refer to the Controls,
Field Power Supply
All
Refer to unit label diagram for additional information. Leads are provided for field wire connections. Use UL (Underwriters Laboratories) approved copper/aluminum connector.
When installing rooftop units, provide safety disconnect per NEC (National Electrical Code) Article 440 or local codes. For
Route power and ground lines through control box end panel or unit basepan (see Fig. 2) to connections as shown on unit wiring diagram and Fig. 8. Factory leads may be wired directly to the disconnect.
8