Charging the System (90MA) - These units are shipped with a full operating charge. If recharging is necessary (complete charge lost), weigh in amount of refrigerant indicated on unit nameplate and in Table 1.
If unit has partial charge, it must be recharged by removing existing charge and recharging by weighing in the required amount of refrigerant. (Refer to Table 1A/B/C/2A/B/C)
Charging the System (90MU)
UNIT SIZES 90MU Units - These units, used with remote condensers, are shipped with a holding charge only. To charge:
1.Open discharge and liquid service valves.
2.Leak test, reclaim refrigerant and evacuate.
3.Using standard refrigerant charging techniques and subcooling charts (Figure 11) add refrigerant as required to maintain proper operating conditions. Subcooling is determined by subtracting the actual temperature entering the TXV from the saturated temperature entering the TXV.
IMPORTANT: Charge on both the HIGH and LOW side simultaneously of idle compressors to prevent axial loading of the scroll, which may cause a temporary no start condition for the compressor. If this occurs, leave the system off for approximately 30 minutes. Attempt to restart the compressor; internal pressures should equalize enough to allow compressor to start.
If removing the compressor, evacuate both the HIGH and LOW side simultaneously.
Required |
| R407C PRESSURE AT LIQUID LINE SERVICE VALVE | PSIG |
| ||||||||||
Subcooling (ºF) | 137 | 149 | 162 | 176 | 205 | 222 | 239 | 256 | 275 | 295 | 315 |
| 336 | 359 |
0 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | 120 |
| 125 | 130 |
5 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 |
| 120 | 125 |
10 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 |
| 115 | 120 |
15 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 |
| 110 | 115 |
20 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 |
| 105 | 110 |
25 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 |
| 100 | 105 |
Required |
| R404A PRESSURE AT LIQUID LINE SERVICE VALVE | PSIG |
| ||||||||||
Subcooling (ºF) | 150 | 163 | 176 | 190 | 205 | 221 | 237 | 255 | 273 | 292 | 313 |
| 334 | 356 |
0 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | 120 |
| 125 | 130 |
5 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 |
| 120 | 125 |
10 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 |
| 115 | 120 |
15 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 |
| 110 | 115 |
20 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 |
| 105 | 110 |
25 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 |
| 100 | 105 |
Required |
| R407C PRESSURE AT LIQUID LINE SERVICE VALVE | kPa |
| |||||||||
Subcooling (ºC) | 1100 | 1200 | 1300 | 1400 | 1500 | 1600 | 1700 | 1800 | 1900 | 2000 | 2100 | 2200 | 2300 |
0 | 23 | 26 | 29 | 32 | 34 | 37 | 39 | 42 | 44 | 46 | 48 | 50 | 52 |
3 | 20 | 23 | 26 | 29 | 31 | 34 | 36 | 39 | 41 | 43 | 45 | 47 | 49 |
5 | 18 | 21 | 24 | 27 | 29 | 32 | 34 | 37 | 39 | 41 | 43 | 45 | 47 |
7 | 16 | 19 | 22 | 25 | 27 | 30 | 32 | 35 | 37 | 39 | 41 | 43 | 45 |
10 | 13 | 16 | 19 | 22 | 24 | 27 | 29 | 32 | 34 | 36 | 38 | 40 | 42 |
13 | 10 | 13 | 16 | 19 | 21 | 24 | 26 | 29 | 31 | 33 | 35 | 37 | 39 |
Required |
| R404A PRESSURE AT LIQUID LINE SERVICE VALVE | kPa |
| |||||||||
Subcooling (ºC) | 1190 | 1288 | 1392 | 1503 | 1580 | 1701 | 1786 | 1918 | 2011 | 2107 | 2206 | 2308 | 2414 |
0 | 23 | 26 | 29 | 32 | 34 | 37 | 39 | 42 | 44 | 46 | 48 | 50 | 52 |
3 | 20 | 23 | 26 | 29 | 31 | 34 | 36 | 39 | 41 | 43 | 45 | 47 | 49 |
5 | 18 | 21 | 24 | 27 | 29 | 32 | 34 | 37 | 39 | 41 | 43 | 45 | 47 |
7 | 16 | 19 | 22 | 25 | 27 | 30 | 32 | 35 | 37 | 39 | 41 | 43 | 45 |
10 | 13 | 16 | 19 | 22 | 24 | 27 | 29 | 32 | 34 | 36 | 38 | 40 | 42 |
13 | 10 | 13 | 16 | 19 | 21 | 24 | 26 | 29 | 31 | 33 | 35 | 37 | 39 |
FIGURE 11 - CHARGING CHARTS
1.Shut off unit main power supply.
WARNING
LOCK OPEN AND TAG unit disconnect before working on fan motor. Remove fuses and take them with you after noting this on tag.
CAUTION
Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.
2.Loosen motor hold down bolts on mounting bracket so that fan belt can be removed.
3Loosen but do not remove the 2 motor mounting bracket bolts on left side of bracket.
4Slide motor/bracket assembly to extreme right, remove bolts and lift out through space between fan scroll and side Rest motor on a high platform such as a step ladder. Do not allow motor to hang by its power wires.
Pressure Relief Device - All units are equipped with a
Crankcase Heater - A Crankcase heater is supplied on 90MA,MU*08 and *12 size units. The heater prevents liquid refrigerant from accumulating in the compressor crankcase during extended shutdown periods. Heater is automatically energized whenever unit main power is on and compressor is stopped. Heater is
Do not shut off main power supply for an extended period except for servicing unit. Turn on power supply for at least 24 hours after an extended shutdown before starting compressor. Refer to “Operation”.
Discharge and Suction Pressure Switches - Refer to Table 1 for opening and closing settings for these safety devices.
The discharge pressure switch is located on the compressor on 06DA compressor equipped units and on the discharge line on all other units. The suction pressure switch is located on top of the compressor on 06DA
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations
Printed in U.S.A. | Pg 15 | |
|
|