Carrier 90MA, 90MU FPT = Female Pipe Thread MPT = Male Pipe Thread, ODF = Outside Diameter Female

Models: 90MU 90MA

1 22
Download 22 pages 24.03 Kb
Page 2
Image 2
LEGEND

TABLE 1A - 90MA/MU PHYSICAL DATA – R-134A , ENGLISH UNITS (See Table 2A for SI units)

 

BASE UNIT (90MA/MU)

 

UNITS

308

 

312

 

NOMINAL CAPACITY

 

Tons

5.5

 

8

 

REFRIGERANT

 

 

R-

 

 

 

OPERATING WEIGHT

 

 

 

 

 

 

 

Base unit 90MA

 

Pounds

895

 

950

 

 

Base Unit 90MU

 

Pounds

N/

 

N/

 

 

Discharge Plenum

 

Pounds

50

 

50

 

COMPRESSOR TYPE

 

 

Semi-Hermetic, Recip

 

 

 

Qty Cylinders

 

 

4

 

6

 

 

Qty Unloading Cylinders

 

 

0

 

2

 

 

Qty Capacity Steps

 

 

1

 

2

 

DISCHARGE

PRESSURE SWITCH

 

 

 

 

 

 

 

Opens (90MA)

 

PSIG

335+/

-10

 

 

 

Closes (90MA)

 

PSIG

235+/-10

 

 

 

Opens (90MU)

 

PSIG

N/

 

 

 

Closes (90MU)

 

PSIG

N/

 

 

SUCTION

PRESSURE SWITCH

 

 

 

 

 

 

 

Opens

 

PSIG

7+/

-3

 

 

 

Closes

 

PSIG

22+/-5

 

 

REFRIGERANT

 

 

 

 

 

 

 

Typ

 

 

R-

 

 

 

 

Qty (90MA ONLY))

 

Pounds

11.2

 

10

 

CONDENSER

(90MA ONLY)

 

 

 

 

 

 

 

Number...Type

 

 

1…Tube

in Tube

 

 

 

Water Volume

 

Gallons

2.42

 

 

EVAPORATOR AIR FAN

 

 

Adjustable, Belt Driven Centrifugal: 1750 RPM Motor@ 60hz

 

 

Nominal Flow

 

CFM

3000

 

4000

 

 

Standard Speed Range

 

RPM

487-690

 

591-838

 

 

Maximum Allowable Speed

 

RPM

1250

 

 

 

Belt Qty/Pulley Pitch Diameter

 

Inches

1 / 8.5

 

1 / 7.0

 

 

Motor Pulley Pitch Diameter Range

 

Inches

2.4 to 3.4 inches

 

 

 

Motor Nominal Rating (@ 60Hz)…Frame Size

 

 

 

 

 

 

 

Standard

 

HP

1…56

 

2…56

 

 

Alternate (SeeNote 1)

 

HP

2…56

 

3…56

 

 

Alternate (See Note 1)

 

HP

3…56

 

N/

 

EVAPORATOR COIL

 

 

3/8 OD, Copper Tubes, Aluminum Fin

 

 

Tube

 

 

Prime

 

 

 

Qty Rows…Fin Spacing

Fins/Inch

3…12.5

 

 

 

Face Area

 

Sq Ft

7.3

 

8.5

 

RETURN

AIR FILTERS

 

 

Factory Supplied, Cleanable

 

 

Qty…Size

 

Inches

4…16 x 20 x 1

 

 

CONDENSER

CONNECTIONS (90MA ONLY)

 

 

 

 

 

 

 

Water Inlet (bottom)

Inches FPT

1

 

1

 

 

Water Outler (top)

Inches FPT

1

 

1

 

 

Maximum Working Pressure (Refrigerant Side)

 

PSIG

400

 

 

CONDENSATE DRAIN CONNECTIONS

Inches FPT

3/4

 

 

ACCESSORY ELECTRIC HEAT

 

 

 

 

 

 

 

Capacity @ 460 volts

 

Watts

17.5

 

 

 

Capacity @ 400 volts

 

Watts

13.4

 

 

 

Number of Electric Heat Stages

 

 

2

 

LEGEND

 

 

 

 

 

FPT = Female Pipe Thread MPT = Male Pipe Thread

ODF = Outside Diameter Female

 

NOTES:

1. Motors other than those furnished with unit must be purchased separately. Contact your Carrier Marine representative

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Printed in U.S.A.

Pg 2

90MA-3SI SUPERCEDES FORM 62-02971-00 09-2009

 

 

Page 2
Image 2
Carrier 90MA, 90MU specifications FPT = Female Pipe Thread MPT = Male Pipe Thread, ODF = Outside Diameter Female