R-407C, R-404A, and R-134a units

compressor equipped units and on the suction line on all other units.

Oil Charge - All units are factory charged with oil. On 06D compressors, observe the oil level in the sight glass at start-up. If unit oil level is below sight glass, add oil until level reaches approximately 1/4 sight glass.

If oil charge is above sight glass, do not remove any oil until the compressor crankcase heater has been energized for at least 24 hours.

When additional oil or a complete charge is required, use only the following Carrier approved oil.

R-407C, R-404A, and R-134a units

Castrol - Icematic SW68

ICI - Emkarate RL68HP

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Printed in U.S.A.

Pg 16

90MA-3SI SUPERCEDES FORM 62-02971-00 09-2009

 

 

Page 16
Image 16
Carrier 90MA, 90MU specifications R-407C, R-404A,and R-134aunits