Carrier Ð Typical 30HXA Refrigerant Piping to Remote Condenser, Saturated Temperature Example

Models: 30HXA HXC076-186

1 28
Download 28 pages 9.99 Kb
Page 11
Image 11
Fig. 7 Ð Typical 30HXA Refrigerant Piping to Remote Condenser

NOTES:

1.Piping shown is for general point-of-connection only and is not in- tended to show details for a speci®c installation. Certi®ed ®eld wir- ing and dimensional drawings are available upon request. The 30HXA units should be installed using certi®ed drawings.

2.Refer to Carrier System Design Manual for details regarding pip- ing techniques.

3.Piping and pressure relief devices are ®eld supplied.

4.Vent pipes properly per local codes.

COOLER*

EXV

OIL SEPARATOR

ANGLE

VALVE

EXV

LIQUID LINE

LIQUID LINE

TO REMOTE

CONDENSER(S)

TO REMOTE

CONDENSER(S)

TO REMOTE

CONDENSER(S)

TO REMOTE

CONDENSER(S)

Table 2 Ð Discharge Line 2 F (1.1 C) Drop in PRESSURE

RELIEF

DISCHARGE

LINE

LEGEND

EXV Ð Electronic Expansion Valve *See Fig. 6 for typical cooler piping.

Fig. 7 Ð Typical 30HXA Refrigerant Piping to Remote Condenser

30HXA REFRIGERANT PIPING (See Fig. 7) Ð Take care when running the refrigerant piping from the 30HXA unit to the remote condenser(s) to avoid excessive pres- sure drops. The pressure drop using R-134a refrigerant is different than when using R-22 refrigerant. See Tables 2 and 3 for an example for a 2 F (1.1 C) pressure drop in saturated temperature in the discharge (hot gas) line and liquid line, respectively. Refer to Fig. 9 and 10 for line sizing informa- tion for the discharge and liquid lines for 30HXA (R-134a) units.

Table 2 Ð Discharge Line 2 F (1.1 C) Drop in

Saturated Temperature Example

SATURATED

 

PRESSURE

 

DISCHARGE

 

 

 

 

 

 

TEMP

R-134a

R-22

 

F

 

C

Psig

kPa

Psig

 

kPa

126

 

52.2

187.5

1293

281.6

 

1942

124

 

51.1

182.0

1255

274.3

 

1891

D PRESSURE

5.5

38

7.3

 

51

LEGEND

COM Ð Common

N.O. Ð Normally Open

Fig. 8 Ð Differential Flow Switch

11

Page 11
Image 11
Carrier HXC076-186 Ð Typical 30HXA Refrigerant Piping to Remote Condenser, Ð Discharge Line 2 F 1.1 C Drop in