| LEGEND |
ALM | Ð Alarm |
CCN | Ð Carrier Comfort Network |
COMM | Ð Communications |
CWFS | Ð Chilled Water (Fluid) Flow Switch |
CWP | Ð Chilled Water (Fluid) Pump |
CWPI | Ð Chilled Water (Fluid) Pump Interlock |
EQUIP | Ð Equipment |
GND, GRD Ð Ground | |
NEC | Ð National Electrical Code (U.S.A.) |
TB | Ð Terminal Block |
| Field Power Wiring |
Field Control Wiring
NOTES:
1.Factory wiring is in accordance with NEC. Field modi®cations or additions must be in compliance with all appli- cable codes.
2.Wiring for main ®eld supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil.
3.Power for control circuit should be supplied from a separate source through a
4.Terminals 13 and 14 of TB2 are for ®eld external connection for remote
5.Terminals 11 and 12 of TB2 are for chilled water ¯ow switch (CWFS) and chilled water pump interlock (CWPI) functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6.Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush.
7.Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va inrush.
Fig. 13 Ð Field Control Wiring
25