Carrier HXC076-186 Ð Field Power Wiring, B Ð Compressor Electrical Data, 30HXA Units cont

Models: 30HXA HXC076-186

1 28
Download 28 pages 9.99 Kb
Page 24
Image 24
Fig. 12 Ð Field Power Wiring

Table 5B Ð Compressor Electrical Data, 30HXA Units (cont)

UNIT SIZE

NAMEPLATE

 

 

COMPRESSOR NUMBERS

 

 

V-Hz

A1

 

 

B1

30HXA

 

 

(3 Phase)

 

 

 

 

 

 

 

RLA

 

LRA

RLA

 

LRA

 

 

 

 

 

208/230-60

*

 

*

*

 

*

 

460-60

157.9

 

1175

157.9

 

1175

186

575-60

126.2

 

940

126.2

 

940

380-60

191.2

 

1299

191.2

 

1299

 

230-50

*

 

*

*

 

*

 

346-50

*

 

*

*

 

*

 

380/415-50

201.2

 

1265

201.2

 

1265

 

208/230-60

349.6

 

743

349.6

 

743

 

460-60

157.9

 

371

157.9

 

371

186-WD

575-60

126.2

 

297

126.2

 

297

380-60

191.2

 

410

191.2

 

410

 

230-50

332.3

 

638

332.3

 

638

 

346-50

220.5

 

439

220.5

 

439

 

380/415-50

201.2

 

400

201.2

 

400

LEGEND

LRA Ð Locked Rotor Amps

RLA Ð Rated Load Amps

WD Ð Wye-Delta Start

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

 

LEGEND

EQUIP

Ð Equipment

NEC

Ð National Electrical Code (U.S.A.)

TB

Ð Terminal Block

Y-Delta

Ð Wye-Delta Start

XL

Ð Across-the-Line Start

Field Power Wiring

Field Control Wiring

Factory-Installed Wiring

NOTES:

1.Factory wiring is in accordance with NEC. Field modi®cations or additions must be in compliance with all applicable codes.

2.Wiring for main ®eld supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil.

Fig. 12 Ð Field Power Wiring

24

Page 24
Image 24
Carrier HXC076-186 installation instructions Ð Field Power Wiring, B Ð Compressor Electrical Data, 30HXA Units cont