Meanings:

PC or PH selects PTAC units (Packaged Terminal Air Conditioners). PH controls a PTAC with 1 speed heat pump with 1 stage of aux heat. PC controls a PTAC with 1 speed air conditioner with 1 stage of E1 heat.

NOTE: A PH thermostat can be converted to control a HeatCool system.

Option 03 - Fahrenheit/Centigrade

Selects temperature measurement units.

Selections:

F = Fahrenheit

C = Centigrade

Default is Fahrenheit

Option 04 - Not used on a PTAC system

Default = OF

Option 07 - Not used on a PTAC system

Default = OF

Option 10 - Reversing valve (HP only)

This selection is only available on heat pump systems. “O/B” terminal can be configured to be energized in either heating mode or in cooling mode, depending on heat pump operation.

C — Thermostat output (O/B) will have 24VAC in cooling mode, 0VAC in heating mode.

H — Thermostat output (O/B) will have 0VAC in cooling mode, 24VAC in heating mode.

Default is C for PTAC.