Table 9E — Medium-Static Drive Data, 60 Hz — SI

UNIT

40RUA*25

40RUA*28

40RUA*30

40RUS*25

40RUS*28

40RUS830

 

MOTOR DRIVE

 

 

 

Motor Pulley Pitch Diameter (mm)

109.2-

109.2-

109.2-

134.6

134.6

134.6

 

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

FAN DRIVE

 

 

 

Pulley Pitch Dia (mm)

239

239

239

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

1—B

2—B

2—B

Belt Pitch (mm)

1062

(2) 986

(2) 986

(2) 1011

(2) 1011

 

 

FAN SPEEDS (r/s)

 

 

 

Factory Setting

14.7

14.7

14.7

Range

13.3-16.4

13.3-16.4

13.3-16.4

Max Allowable Speed (r/s)

20.0

18.3

18.3

Change per 1/2 Turn of

0.255

0.255

0.255

Moveable Motor Pulley

Flange

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

SHAFTS CENTER DISTANCE (mm)

232-279

169-240

169-240

Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.

Table 9F — High-Static Drive Data, 60 Hz — SI

UNIT

40RUA*25

40RUA*28

40RUA*30

40RUS*25

40RUS*28

40RUS*30

 

MOTOR DRIVE

 

 

 

Motor Pulley Pitch Diameter (mm)

109.2-

109.2-

109.2-

134.6

134.6

134.6

 

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

FAN DRIVE

 

 

 

Pulley Pitch Dia (mm)

188

203

203

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

2—B

2—B

2—B

Belt Pitch (mm)

935

935

960

FAN SPEEDS (r/s)

 

 

 

Factory Setting

18.6

17.1

17.1

Range

16.9-

14.6-

14.6-

20.0

17.9

17.9

 

Max Allowable Speed (r/s)

20.0

18.3

18.3

Change per 1/2 Turn of

0.323

0.278

0.278

Moveable Motor Pulley

Flange

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

SHAFTS CENTER DISTANCE (mm)

207-255

169-240

169-240

It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.