Carrier R-410A manual Check Voltage Imbalance, Comp A1 Comp B1

Models: R-410A

1 36
Download 36 pages 61.59 Kb
Page 36
Image 36

CHECK VOLTAGE IMBALANCE

 

 

 

LINE-TO-LINE VOLTS:

AB ________ V

AC ______ V

BC

______ V

(AB + AC + BC)/3 = AVERAGE VOLTAGE = _______ V

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _______ V

 

 

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

__________ %

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START-UP

CHECK INDOOR FAN MOTOR SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

INTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

COMPRESSOR AMPS (L1/L2/L3)____/____/____ ____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING

OIL LEVEL AT 1/

to 1/ FULL?

(Y/N) ______

8

3

 

NOTES:

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231

Printed in Mexico

Edition Date: 09/09

 

Catalog No: 40RU-03SI

 

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Pg CL-2

Replaces: New

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Page 36
Image 36
Carrier R-410A manual Check Voltage Imbalance, Comp A1 Comp B1