INSTALLATION

INSTALLATION

BOILER ROOM

Important

Keep vents free at all times.

Do not store inflammable products in the boiler room.

Do not store corrosive products near the boiler, such as paints, solvents, chlorine, salt, soap and other cleaning products.

If you smell gas, do not switch on the light or light a flame. Turn off the mains gas tap at the meter and inform the appropriate services immediately.

Access

The boiler room must be large enough to allow good access to the boiler. The following minimum distances are required around the boiler:

- front

500 mm

- side

100 mm

- behind

150 mm

- above

700 mm

Ventilation

CHIMNEY CONNECTIONS

IMPORTANT

Boilers must be installed by an approved heating engineer, in accordance with the prevailing local standards and regulations.

Flue size should not be less then the outlet size of the boiler.

Chimney connection type: B23

The boiler is connected to the chimney by a metal pipe rising at an angle from the boiler to the chimney.

A flue disconnection piece is required.

This must be easy to remove to give access to the flue pipes when servicing the boiler.

The boiler room must be fitted with top and bottom vents according to the prevailing local standards and regulations.

The table below gives an example conforming to the Belgian standards.

Ventilation

 

71

101

Min. fresh air requirement

m3/h

126

194

Bottom vent

dm2

2.4

3.20

Top vent

dm2

2.0

2.0

 

 

 

 

Other countries should refer to their own standards.

Base

The base on which the boiler rests must be made of non-combustible materials.

A. Top vent

B. Bottom vent

C.Draught regulator D. Inspection opening E. Lined chimney height F. Chimney diameter

A

B

F

E

CAccessVentilation

D

Chimney / minimum flue diameter

71

101

E = 5 m Ø F min.

mm

189

234

E = 10 m Ø F min.

mm

159

178

E = 15 m Ø F min.

mm

150

150

 

 

 

 

Note:

Regulations vary from country to country therefore the table above is intended only as a guide.

Due to the high efficiency of our boilers, the flue gasses exit at low temperature. Accordingly, there is risk that the flue gasses could condense, which could damage the chimney. In order to avoid this risk, it is strongly recommended that the chimney be lined.