Power supply

INSTALLATION

ELECTRICAL CONNECTION

Power supply

The boiler operates with a 230 V - 50 Hz single phase supply. A double pole isolator with a 6 amp fuse or a 6 amp MCB must be fitted outside the boiler to allow power to be shut off during servicing and before any repairs are carried out on the boiler.

Conformity

Boiler installation must comply with the prevailing local standards and legislation.

Safety

The stainless steel tank must be earthed separately.

The power to the boiler must be switched off before any work is carried out.

Alarm - module

Connect the flat ribbon cable from the alarm-module “X7” to MCBA connector “X8”.

The volt free relays mounted on the alarm module will now be actived as described below:

1 - Alarm:

This contact closes if the MCBA is in lock out.

2 - External gas valve / burner - run indication:

This contact closes if a heat request is present and the fan is running.

3 - Domestic Hot Water pump:

This contact closes if a Domestic Hot water heat request is present.

• Technical data:

 

-

Ambient temperature:

0…60 °C

-

Contact ratings:

IRMS 1A

 

 

230 V (+10% / 15%) 50 Hz

If inductive loads are connected, take precautions over these loads against peak voltages (e.g. RC-network).

1

Internal MCBA connections

Alarm - module

X1: Connection MCBA 230 Volt

X2: 24 Volt connector

X3: NTC - connector

X4: NTC 5 - analogue in connector

X5: Communication / NTC 4 - connector

Connection for transformer

X1

X2

X3

X4

X5

MCBA

2

3

X8: Ribbon cable connection for alarm module (option)

X7: Display connection

10