UVSTR / UVCVR Series Vent-Free Fireboxes

3A

(Front View)

CEILING

42" Min. 36"

11" Min.

(Side View)

HEADER

 

 

 

 

 

 

 

 

 

 

DRYWALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8"

 

 

 

 

 

MANTEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1¹⁄"

 

 

 

 

SHELF

 

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

 

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STAND-OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Seal with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

noncombustible

 

 

 

 

 

 

 

 

 

 

material

 

 

 

 

 

3B

(Top View)

FINISHED WALL

COMBUSTIBLE

MANTEL

MANTEL TRIM

TRIM

 

LEG

 

FIREBOX

2"

2"

4¹⁄"

 

 

 

4¹⁄"

 

 

NONCOMBUSTIBLE

FACING MATERIAL

(Side View)

Front leg

of grate

3"

FP679

Fig. 3 Clearances to combustibles.

Minimum Clearances

Sidewall Clearances:

The clearance from the side of the firebox to any com- bustible wall should not be less than 11" . (Fig. 3A)

Ceiling Clearances:

The ceiling height should not be less than 42" from the top of the fireplace opening. (Fig. 3A)

Mantel Clearances:

If a combustible mantel is installed, it must meet the clearance requirements detailed in Figure 3A. A mantel breastplate can be installed at a minimum height of 8" with a maximum projection of 1¹⁄₂".

Grate Clearance:

AB

 

 

FP1545

 

 

 

 

Front/Back Width

Side Width

 

A

B

UVSTR/UVCVR36

29"

17¹⁄₈"

 

 

 

Fig. 4 Hearth dimensions.

The minimum clearance between the front legs of the grate and front edge of the fireplace is 3" . (Fig. 3B)

7412960

5

Page 5
Image 5
CFM UVCVR36, UVSTR36 dimensions Uvstr / Uvcvr Series Vent-Free Fireboxes, Minimum Clearances