CFM UVCVR36 Install Hood, UVSTR / UVCVR Series Vent-Free Fireboxes, 7412960, Hood location

Models: UVCVR36 UVSTR36

1 16
Download 16 pages 28.17 Kb
Page 9
Image 9
Fig. 11 Appliance surround flush with finish wall.

Finished Wall

Must be sealed with noncombustible mate- rial

Noncombustible Decorative Fac- ing

Surround

2 x 4 Finished

Header

Fig. 13 Side view of firebox with extended hood. Standoff

FP610

UVSTR / UVCVR Series Vent-Free Fireboxes

4¹⁄₄" Max. Fig. 12 Facing on firebox flush with finished wall.Install HoodFig. 14 Hood location.

Brick Sur- face

Extended

Hood

Fig. 11 Appliance surround flush with finish wall.

Finished Wall

Noncombustible Decorative Fac- ing

Surround

2 x 4 Finished Header

Covered Wall

Manual backgroundManual background Must be sealed with non- combustible material

Manual background Standoff

FP611

FP685

Fig. 13 Side view of firebox with extended hood.

Fig. 12 Facing on firebox flush with finished wall.

Install Hood

A 2" or 4" Hood can be purchased for the UVSTR36 and the UVCVR36. A Hood must be installed if the mantel falls within the dimensions and location shown in Figure 3. Failure to do so may create a fire hazard.

WARNING: When the black surround is covered by a brick surface, (Fig. 13), use an extended hood. The hood should extend out to the brick surface (Refer to Figs. 13 and 14) and be attached to the firebox. The maximum brick to noncombustible sur- face that may extend out past the black surround surface is 4¹⁄₄".

The size of the Hood required depends on BTU ratings and clearances. See the Accessories section on Page 13 for details.

Screw Manual background Slot (Fastens to

side rail from inside hood)

Use Top Slot Manual background

Manual backgroundManual background Screw

FP613

Fig. 14 Hood location.

7412960

9

Page 9
Image 9
CFM UVCVR36 Install Hood, UVSTR / UVCVR Series Vent-Free Fireboxes, 7412960, Appliance surround flush with finish wall