Majestic® Fireplaces Power Venting System
Installation Instructions
General information and instructions for the power vent system model No.
1.This power vent system must be installed by a quali- fied installer in accordance with all applicable local codes and with the current installation codes for gas burning appliances
Electrical connections and grounding must be in ac- cordance with the Canadian Electrical Code, C22.1 Part 1 and in U.S.A., National Electrical Code ANSI/ NFPA70 and/or local codes where applicable.
2.This device must be installed by a qualified profes- sional installer in accordance with these instructions. If improperly installed, a hazardous condition such as an explosion or carbon monoxide poison could result.
3.The Power Vent System
4.Plan the vent system so that code required distanc- es are maintained from plumbing and wiring.
5.The Power Venter motor shaft must be mounted horizontally to ensure proper operation of the fan pressure proving switch and to prevent motor bear- ing wear.
6.Flue gas temperatures must not exceed 470ºF at Power Venter inlet. Ambient temperature must not exceed 104ºF.
7.Disconnect power supply when making wiring con- nections or when working around the fan blade and motor. Failure to do so may result in severe personal injury and equipment damage.
8.Make certain the power source is adequate for the fan motor requirements. Do not add the Power Ven- ter to a circuit where the total load is unknown.
9.This Power Venter System
Power Vent System Parts and Description
1.Fan Assembly - comes complete with 6’ (1.8 m) power cord for plugging into a standard house receptacle. The system is completely
2.24 Volt Wiring Harness - a 40’ (12m) wiring harness with
3.Vent Terminal - the device which exhausts flue gases into the atmosphere.
4.Fan Mounting Bracket - to secure the fan in a vibra-
5.
6.Approved 4” (102 mm) diameter insulated aluminum flex liner, 4” (102 mm) diameter
7.Assorted clamps, connectors and wall mounting brackets.
General Venting Information
Always consult your local codes and authorities, in the absence of such codes, follow the current installa- tion codes for gas burning appliances
1.Clearance to Combustible Materials:
•1” (25 mm) for insulated single wall vent or flexible vent pipe.
•6” (152 mm) for single wall fan housing.
•1” (25 mm) for fan motor.
•1” (25 mm) for
•6” (152 mm) for single wall vent or flexible vent pipe.
*
2.Total allowable system length is 100’ (30 m) of straight pipe. Minimum allowable system length is 5’ (1.5 m).
NOTE: Deduct 10’ (3 m) for each 90° elbow and 5’ (1.5 m) for each 45° elbow.
Example: An installation requires 30’ (9 m) of straight pipe with 45° and three (3) 90° elbow.
Straight pipe | 30’ (9 m) |
45º Elbow (1) | 5’ (1.5 m) |
90º Elbow (3) | 30’ (9 m) |
TOTAL | 65’ (19.5 m) |
Total equivalent pipe length = 65’ (19.5 m)
2 | 51810 |