P R O G R A M M I N G

FAILSAFE WIRING TYPES

TYPE

TS Momentary contact to open, close, and stop with open override and Timer To Close. Every device that causes door to open, including a reversing device, activates the Timer To Close. Auxiliary controls can be connected to open input to activate the Timer To Close. If the timer has been activated, the open button and radio control can recycle the timer. The stop button will deactivate the Timer To Close until the next command input. The Timer To Close will function from the programmable mid stop with this wiring type. Compatible with 3-Button Station, 1-Button Station and 1 & 3-Button Remote Controls. (NOTE: Requires Optional self monitoring photo eyes to operate.)

T

Momentary contact to open, close, and stop, with

 

open override and Timer To Close. Every device that

 

causes the door to open, except a reversing device,

 

activates the Timer To Close. Auxiliary controls can

 

be connected to open input to activate the Timer To

 

Close. If the Timer To Close has been activated, the

 

open button and radio control can recycle the timer.

 

The stop button will deactivate the timer until the

 

next command input. The Timer to Close will

 

function from the programmable mid stop with this

 

wiring type. Compatible with 3-Button Station,

 

1-Button Station and 1 & 3-Button Remote

 

Controls. (NOTE: Requires Optional self monitoring

 

photo eyes to operate.)

FSTS

Momentary button contact for open, close and stop

 

programming. Radio controls allowing open, close

 

and stop. User set mid stop. User set Timer To

 

Close. The single button station opens the door to

 

the full open limit bypassing the mid stop and

 

activates the Timer To Close, putting the operator in

 

TS mode until the door reaches the down limit, or

 

is stopped in travel. At which time the operator

 

enters the B2 mode. Compatible with 3-Button

 

Station, 1-Button Station and 1 & 3-Button

 

Remote Controls. (NOTE: Requires Optional self

 

monitoring photo eyes to operate this feature/wire

 

type.)

C2 Failsafe

Same functions as C2. Self Monitoring safety device

 

must be installed to operate door for each of the

 

following failsafe wiring types. See Self Monitoring

 

Safety Device Options. Compatible with 3-Button

 

Station, 1-Button Station and 1 & 3-Button

 

Remote Controls.

B2 Failsafe Same functions as B2. Self Monitoring safety device must be installed to operate door for each of the following failsafe wiring types. See Self Monitoring Safety Device Options. Compatible with 3-Button

Station, 1-Button Station and 1 & 3-Button

Remote Controls.

D1 Failsafe Same functions as D1. Self Monitoring safety device must be installed to operate door for each of the following failsafe wiring types. See Self Monitoring Safety Device Options. Compatible with 2-Button Station & 2-Button Remote.

E2 Failsafe Same functions as E2. Self Monitoring safety device must be installed to operate door for each of the following failsafe wiring types. See Self Monitoring Safety Device Options. Compatible with 3-Button

Station & 3-Button Remote.

SELF-MONITORING SAFETY DEVICE OPTIONS

To use the operator in any of the Failsafe wiring modes, or Timer To Close wiring modes (TS, T, FSTS), a self monitoring safety device or CPS3 card with photo eyes or safety edges must be installed.

RECOMMENDED SELF-MONITORING SAFETY DEVICES:

CPS-LNEMA 1 Direct Connect Eyes

CPS-LN4NEMA 4 Direct Connect Eyes

IMPORTANT NOTES:

1.External interlocks may be used with all functional modes.

2.Auxiliary devices are any devices that have only dry contacts. Examples: photocell, loop detector, pneumatic or electrical treadles, radio controls, one button stations, pull cords, etc.

3.Open override means that the door may be reversed while closing by activating an opening device without the need to use the stop button first.