MDS-6AINSTALLATION MANUAL

2.2- WIRING MCS CONTROLLERS TO THE MDS-6A

System Specs

IMPORTANT NOTE

MCS Controllers and IR Receivers

Each ZONE KEYPAD INPUT RJ45 jack on the MDS-6A provides 12VDC/300mA.

You may choose to load each of the MDS-6A’s ZONE KEYPAD INPUTS with any combination of MCS Controllers and/or IR Receivers as long as the TOTAL CURRENT CONSUMP-

TION DOES NOT EXCEED 300mA.

MCS Controller (w/ IRTUBE) = 125mA

Additional IR Receivers = 10mA

Each of the MDS-6A’s Zone Controller RJ-45 Jacks provides 12VDC/300mA. These Zone Keypad connections are capable of driving a maximum of TWO MCS Controllers per zone.

MCS Controller Connections and MDS-6A Wiring

1.CAT-5 should be used for all MCS Controller wire runs (max 500ft).

2.MCS Controller wire runs can be terminated directly to RJ45 connectors and then plugged into the MDS-6A.

3.Use RJ45-to-Pigtails Interface Cables and a point-to-point punchdown block to facilitate the termination of MCS Controller wire runs. Use of a punchdown block eliminates crimping and pinout errors while providing a neat, on-wall wire management solution.

MCS Controller to MDS-6A Connections

Butt Splice

 

 

 

 

 

 

ZONE

Blue (N/C)

or

 

MCS

 

Equivalent

KEYPAD

White/Blue (IR)

 

 

Controller

INPUTS

Orange (Clone Data)

CAT-5

 

 

 

 

White/Orange(RS485+)

 

 

 

RJ45

Green(RS485-)

 

 

RJ45

 

White/Green (+12V)

 

 

A.

Pigtail

Brown (GND)

 

 

Pigtail

 

White/Brown (N/C)

 

 

 

MCS Controller to MDS-6A Connections w/ Punchdown Block

 

 

INPUTS

 

Blue (N/C)

Blue (N/C)

MCS

 

White/Blue (IR)

White/Blue(IR)

CONTROLLER

KEYPAD

 

Orange (Clone Data)

Orange (Clone Data)

 

 

 

White/Orange (RS485+)

White/Orange (RS485+)

 

 

 

Green (RS485-)

Green(RS485-)

 

 

 

White/Green (+12V)

White/Green(+12V)

 

 

ZONE

 

Brown (GND)

Brown (GND)

 

 

 

White/Brown (N/C)

White/Brown (N/C)

 

 

 

 

 

 

 

B.

 

Punchdown Block

 

 

 

 

 

 

 

CONNECTING TWO MCS CONTROLLERS IN ONE ZONE

 

 

Connect the IR, Ground, RS485+, and RS485- wires together in parallel

INPUTS

 

 

White/Blue (IR)

 

MCS

 

 

Orange (Clone Data)

 

Controller

KEYPAD

 

 

White/Orange (RS485+)

 

 

 

 

Green (RS485-)

 

 

 

 

White/Green(+12V)

 

 

 

 

Brown (GND)

 

 

ZONE

 

 

 

 

 

 

White/Blue(IR)

 

MCS

 

 

 

Orange (Clone Data)

 

Controller

 

Punchdown Block

White/Orange (RS485+)

 

 

 

 

 

Green (RS485-)

 

 

C.

Figure 6

White/Green (+12V)

 

 

Brown (GND)

 

 

© Channel Plus, Inc 2004 • All rights reserved. 4/04

Page 9

Page 9
Image 9
Channel Plus installation manual Wiring MCS Controllers to the MDS-6A, System Specs, MCS Controllers and IR Receivers