![Fig. 9. InjectorTee.](/images/new-backgrounds/43629/4362921x1.webp)
| 22mm Open Vents | ||
Feed and Expansion Tank |
| Cold Water Tank | |
|
| ||
Overflow |
| Overflow | |
|
| ||
|
| Domestic Hot Water Draw Off | |
Gravity Radiator |
|
| |
|
| Drain Cock | |
|
| Indirect Hot Water Cylinder | |
Minimum Return |
| Central Heating Flow | |
|
| ||
Thermostat |
| Circulating Pump | |
|
| ||
|
| Central Heating Return | |
|
| Drain Cock at Lowest Point | |
Fig. 7 Typical Central Heating and Hot Water System | |||
| Using 4 Boiler Tappings | ||
|
| 22mm Open Vents | |
Feed and Expansion Tank | Cold Water Tank | ||
|
| ||
| Overflow | Overflow | |
|
| ||
|
| Domestic Hot Water Draw Off | |
Gravity Radiator |
| ||
|
| Drain Cock | |
|
| Indirect Hot Water Cylinder | |
Minimum Return Thermostat | Central Heating Flow | ||
Circulating Pump | |||
| |||
Central Heating Return |
|
| |
Drain Cock at Lowest Point | Injector Tee | ||
|
| ||
Fig. 8. Typical Central Heating & Hot Water System | |||
| Using 3 Tappings | ||
| Gravity Return | ||
| (28mm Pipe) | ||
Central Heating Return |
| Common Return to Boiler | |
|
| (28mm Pipe) | |
| Fig. 9. InjectorTee. | ||
|
| Page 9 | |
|
| LA30iB 3.99 |
with the
Ensure that the flue pipe is not obstructed or restricted in any way and that all joints are well sealed.
Before infilling cover the front of the fire to protect it. Ensure that the flue pipe is central and then fill the space between the body of the fire and the structural brickwork with vermiculite (eg. micafil or similar) concrete. Ensure that there are no air pockets. The recommended mix is six volumes of vermiculite granules to one volume of portland cement thoroughly mixed together. Enough water should be added so that no more than one or two drops of water are released when a handful of the mixture is squeezed.
After filling with vermiculite flaunch the top of the flue connector pipe to the chimney with lime mortar.
Make good the holes in the front and side of the chimney breast making sure that they are completely airtight. A typical installation is shown in Fig. 10.
In most installations it will be possible to sweep the chimney through the appliance. If this is not possible then some alternative means (such as a soot door), must be provided.
The
THERMOSTAT
Before lighting the fire check the cold setting distance of the thermostat.
With the control knob at the maximum setting the flap should be 18 mm from the air inlet as shown in Fig. 11. To adjust the distance slacken the locking nut and adjust as necessary. When set correctly