Chromalox 8003 user manual Operator Parameters

Models: 8003

1 19
Download 19 pages 53.58 Kb
Page 14
Image 14

8003 Operator Parameters

Push the FUNC pushbutton. The lower display shows the cue, the upper display shows the value of the selected parameter.

Cue

Description

SP

Control Setpoint, range from "rL" to "rH".

nnnSoftware key for parameter protection set in Conf mode P18.

A1

Alarm 1 Setpoint, range from Conf mode P2 to P3.

A2

Alarm 2 Setpoint, range from Conf mode P2 to P3.

H1

Alarm 1 hysteresis (deadband) 0.1 to 10.0% of

 

alarm span.

H2

Alarm 2 hysteresis (deadband) 0.1 to 10.0% of

 

alarm span.

Pb

Proportional Band, range from 1.0 to 99.9% of

 

span for heating output, 1.5 to 99.9% of span

 

for heating/cooling output. If Pb = 0, ON/OFF

 

control is enabled and ti, td, C, C2, rC, OLP,

 

OLH and IOL are not displayed.

HS

Hysteresis (deadband) for ON/OFF control

 

(active if Pb = 0), range 0.1 to 10.0% of span.

ti

Integral time (automatic reset), range 1 minute

 

and 20 seconds to 20 minutes and 00 seconds,

 

or if blank integral is disabled.

td

Derivative (rate), range 1 second to 9 minutes

 

and 59 seconds. If 0, derivative is disabled.

CHeating cycle time, range 1 to 200 seconds (30 seconds or greater recommended for relay outputs).

C2

Cycle Time for Output 2 (heat/cool control

 

selected), range 1 to 200 seconds (30 seconds

 

or greater recommended for relay outputs).

rC

Relative cooling gain (for heat/cool) control

 

range 0.20 to 1.00.

OLP

Overlap/Deadzone (for heat/cool) Positive value

 

is amount of overlap; negative value separation

 

between heat and cool Pbs, range -20 to 50% of Pb.

rL

SP minimum value (low limit)

rH

SP maximum value (high limit)

rP

Ramp on setpoint changes, range 1 to 100

 

degrees/minute or blank (step change).

OLH

Output power max. value, range 0 to 100%

 

heating, -100 to 100% heat/cool, limits power

 

continuously (tOL = blank) or on startup per

 

tOL settings.

tOL

Time interval for OLH power output limit, range

 

1 to 100 minutes or if blank infinite. The timer

 

starts if the actual temperature is less than P15

 

(threshold value).

Chromalox 8003 User's Manual

11

Page 14
Image 14
Chromalox 8003 user manual Operator Parameters