General Operation
There are two setup modes for the 8003:
•Configuration Mode
•Operator Mode
In general, the Configuration Mode is the initial setup of the controller when first installed. Input type and alarm setup are examples of Configuration Mode settings. The Operator Mode includes settings that might be adjusted frequently with daily control operations such as setpoints and PID parameters.
Notes for Configuration Mode:
FUNC = | Stores the new value of a selected parameter |
| and increments to the next parameter. |
SMRT = | Scrolls parameters back (in reverse order) |
| without storing the new parameter value. |
▲= Increases the value of the selected parameter. ▼ = Decreases the value of the selected parameter.
Configuration Procedure
1.Remove the instrument from its case.
2.Set the internal switch V2 (see the following figure) in open position.
4
PZ1
PZ3
PZ4
PZ6
PZ7
PZ10V2
PZ11
3.Reinsert the instrument in its case.
4.Switch on the instrument. “CNF” should be displayed in the upper display.
Note: If "CAL" indication is immediately displayed, press the ▲ pushbutton to return to the configuration mode (CNF).
5.Push the FUNC pushbutton.
The lower display shows the parameter code while the upper display shows the actual parameter value.
Chromalox 8003 User's Manual