Chromalox 8003 user manual P9 = Alarm 1 Inhibit

Models: 8003

1 19
Download 19 pages 53.58 Kb
Page 9
Image 9
P9 = Alarm 1 Inhibit

P9 = Alarm 1 Inhibit

Available only when P7 is different from 0.

OFF = inhibit disabled

ON = inhibit enabled

Note: The Alarm Inhibit disables the alarm action after a setpoint change. At startup, it automatically enables the alarm when the process temperature reaches the present condition.

P10 = Alarm 2 Type

 

 

0 = Not provided

2

= Band alarm

1= Process alarm

3

= Deviation alarm

P11 = Alarm 2 Operative Mode Available only when P10 is different from 0.

P13 = Type of OFFSET Applied to the Measured Value P13 = 0 = constant OFFSET (P14) all over the range P13 different from 0 = P13 shows the application point of the offset value set by P14 parameter.

P14 = OFFSET Value

When P13 = 0, P14 is programmable, in engineering units, from -20 % to +20 % of the input range.

When P13 is different from 0, P14 is programmable from -20 % to + 20 % of P13 value.

-20% to +20%

H = High Alarm

L = Low Alarm

P12 = Alarm 2 Inhibit

Available only when P10 is different from 0 OFF = Inhibit disabled

ON = Inhibit enabled

Note: The Alarm Inhibit disables the alarm action after a setpoint change. At startup, it automatically enables the alarm when the process temperature reaches the present condition.

Readout

Real curve

 

 

P14

 

Adjusted

 

 

 

 

curve

Input

P13 = 0

Readout

Real curve

P14

 

 

 

 

 

 

 

 

 

 

 

 

Adjusted curve

Input

P13

6

Chromalox 8003 User's Manual

Page 9
Image 9