INSTRUCTIONS FOR INSTALLING WALL MOUNTED STAR-GF
1.Check voltage on heater nameplate and
2.The
3.See Instruction Sheet PG434 (provided with heater) for IMPORTANT INSTRUCTIONS and WIRING.
4.Using the
5.Wire between
6.The ground fault sensor has been factory set at .03 Amps, DO
NOT CHANGE THE SETTING.
|
|
| ||
|
|
| 6" | |
|
|
| 3/4 | |
Table 2 |
|
|
| |
Heater Model | Max. No. of Heaters |
|
| |
6 |
|
| ||
3 | 10" | |||
2 | ||||
|
| |||
1 |
|
| ||
|
|
| 3/4 | |
|
| 5/16 Dia. | 6" | |
|
|
|
MAINTENANCE
The Chromalox
The
ELECTRIC SHOCK HAZARD. Disconnect all power to heater before installing or servicing kit(s).
Failure to do so could result in personal injury or property damage. Kit(s) must be installed by a qualified person in accordance with the National Electrical Code, NFPA 70.
If heating element(s) fail to operate:
1.Open door of enclosure. DANGER: Hazard of Electric Shock. If "Tripped" indicator is on, this indicates one or more heating elements are about to fail. Disconnect power and fol- low the GF Troubleshooting Diagram below.
2.If the "Tripped" indicator is not on, check for blown fuses or failed components within the heater's electrical system.
GF TROUBLESHOOTING DIAGRAM
Yes
Is the set point of
the GF sensor set No at a value less than
.03 amps?
START
Tripped Indicator
Light is On
Is this the
initial
installation?
Call Chromalox Service Dept.
1
No
Is this the first time heater is used for the season?
No
This condition indicates at least one element is
about to fail.
Did the problem occur after working properly during part of this heating season?
Yes
Yes
Yes
Unbuss wiring, check insulation resistance on each element.
1.Turn set point dial clockwise to .03 amps.
2.Flip toggle switch mounted ontop of enclosure back and forth one time, (this resets the GF sensor).
No
Does the heater
operate?
Yes
Close cover.
Unbuss wiring, check insulation resistance on each element.
1.Each element to have at least 10 Meg terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the rated voltage for one hour.
3. Rebuss elements,
Does the
heater
operate?
Yes
Close cover.
No
Do you want to
reduce future No down time and maintenance
costs?
Yes
1.Replace all elements.
2.Flip toggle switch back and forth, one time to reset GF sensor.
Does the heater | No | |
operate? |
| |
| Yes |
|
|
| |
|
|
|
1.Each element to have at least 10 Meg terminal to sheath.
2.If element does not have at least 10 Meg. dry out element by applying half of the rated voltage for one hour.
3.Rebuss elements,
| No |
| Does the | ||
|
|
|
| heater | |
|
|
|
| operate? | |
|
|
|
|
|
|
|
|
|
|
|
|
Call Chromalox |
|
| Yes | ||
Service Dept. |
|
| |||
|
|
| |||
1 |
|
|
| ||
|
|
|
|
|
|
|
|
| Close cover. |
Close cover.