OPTIONAL EQUIPMENT FOR CHROMALOX STEAM BOILERS (cont’d.)
5.Connect the ohmmeter between controller terminals W and R and raise the set point of the controller above the actual pressure being measured. The ohmmeter should read the full value of the poten- tiometer measured in step 4 (135 ohms for an L91B).
6.Slowly lower the set point of the controller while observing the ohmmeter reading. The resistance should drop to zero at some set point below the actual pressure.
7.An approximation of the proportioning range can be made by observing the change in set point required for a resistance change from zero to full value.
8.When the controller is operating properly, reconnect the wires, replace the cover. tighten the cover screw, and reset the controller to the desired value.
9.Reconnect power to the controlled motor.
Main Scale |
|
Adjusting Screw | Proportioning Range |
| Adjusting Screw |
Main Scale | R |
Setting | W |
Indicator | B |
Ohmmeter | Setpoint |
| W R B |
| Increases |
| to 15 Ohms |
Note: Terminals are not labeled, but
Figure 18
BOILER SEQUENCER (5 STEP)
RECYCLE FEATURE (See Figure 19)
The step control is designed to drop out all contactors when con- trol circuit is interrupted. On resumption of power, the camshaft rotates to the
TESTING OPERATION OF SEQUENCER (See Figure 20)
1.With boiler off, remove wiring from pressure control on sequencer low voltage terminal board.
2.Turn on boiler to supply the voltage to sequencer. Short terminal R and B for
3.If sequencer operates under this test procedure, but when rewired to pressure controller, does not function, check pressure control. Note that wiring is
Figure 20
Typical Wiring Diagram for 5 Step Motor Driven Sequencer
SEQUENCE REVERSER (See Figure 21)
GENERAL:
Sequence Reverser is an automatic switching device which is interposed on an electric boiler between the proportional sequence controller and the heating element contactors. The device is periodi- cally actuated to alter the operating sequence of each of the heating elements, thereby increasing the overall reliability of the boiler.
DETAILS:
The Sequence Reverser consists of an
Figure 19 – Five Step Sequencer
9