Wiring a DC-Powered System

Wiring a DC-Powered System

Wiring a DC-Powered System

The procedure in this section explains how to wire a DC-powered LS2020 switch to a DC power source. This task should be performed only by qualified service personnel or a licensed electrician.

This section applies only to systems with the DC power option. If you have a standard AC-powered system, skip to the section “Installing Fantails.”

For general information on DC-powered LS2020 systems, see the LightStream 2020 Hardware Reference and Troubleshooting Guide. For power specifications, see the LightStream 2020 Site Planning and Cabling Guide.

Preparation for Wiring

Note the following in preparation for wiring a DC-powered LS2020 switch:

The system power connection on the DC power tray is provided by a 3-position terminal block, as shown in Figure 2-3. The –48, –48RTN, and CHS GND connections providing –48VDC power to the system require a minimum of number 10AWG wire for the 24A-rated load. The terminal block is rated to accept up to number 8AWG solid wire. The use of ferrules to terminate these wires is recommended.

The alarm circuit connection to the DC power tray is provided by a smaller 3-position terminal block, also shown in Figure 2-3. The COM, NO, and NC connections providing the circuit breaker alarm indication should be wired with number 22AWG or larger wire. The use of number 6 spade or ring lug terminals for these connections is recommended.

Obtain a slot-tip screwdriver for securing the system power terminals and a Phillips screwdriver for securing the alarm circuit terminals.