2-5
Catalyst 3750-E and Catalyst 3560-E Switch Hardware Installation Guide
OL-9774-03
Chapter 2 Switch Installation
Preparing for Installation
Installation Guidelines
Before installing the switch, verify that these guidelines are met:
Clearance to front and rear panels is such that
Front-panel indicators can be easily read.
Access to ports is sufficient for unrestricted cabling.
AC power cord can reach from the AC power outlet to the connector on the switch rear panel.
The X2-10GB-CX4 transceiver module minimum bend radius and connector length is met. See
the X2 transceiver module documentation for more information.
For switches that support the RPS 2300, confirm that you have access to the switch rear panel to
connect the RPS 2300. If you do not have access to the rear panel, you should cable the switches
before you rack-mount them.
For switches with the optional 1150-W power-supply module (C3K-PWR-1150WAC=), first
rack-mount the switch before installing the power-supply module.
For power-supply modules and fan modules, tighten the module captive screws before moving the
switch.
When connecting or disconnecting the power cord on a switch that is installed above or below a
1150-W power supply-equipped switch, you might need to remove the module from the switch to
access the power cord.
Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent
lighting fixtures. Make sure that the cabling is safely away from other devices that might damage
the cables.
For copper connections on Ethernet ports, cable lengths from the switch to connected devices can
be up to 328 feet (100 meters).
For cable requirements for X2 module connections, see the “Cable and Adapter Specifications”
section on page B-5. Each port must match the wave-length specifications on the other end of the
cable, and the cable must not exceed the required cable length.
Operating environment is within the ranges listed in Appendix A, “Technical Specifications.”
Airflow around the switch and through the vents is unrestricted.
Temperature around the unit does not exceed 113°F (45°C). If the switch is installed in a closed or
multirack assembly, the temperature around it might be greater than normal room temperature.
Box Contents
The box contents are described in the switch getting started guide. If any item is missing or damaged,
contact your Cisco representative or reseller for support.
Tools and Equipment
You need to supply a number-2 Phillips screwdriver to rack-mount the switch. For connecting the
StackWise cables, you need a ratcheting torque screwdriver capable of 5 lbf-in. (80 ozf-in.).