Chapter 4 Installation on Cisco 3660 Routers
Installing the Alarm Terminal Block
Follow this procedure to install the alarm terminal block (see Figure
Step 1 Turn OFF power to the router. However, to channel ESD voltages to ground, do not unplug the power cable.
Step 2 | Use 12- or | |
Step 3 | Strip the wire shielding so that approximately 0.38 in. (9.7 mm) of each wire is exposed. | |
| Figure | |
|
|
|
|
| 22661 |
|
| |
|
| |
| NO P NC |
Step 4 Press the
Note Always wire the P terminal and one of the other (NO and NC) terminals.
Note To remove wires, press the
Step 5 Plug the alarm terminal block into the alarm port on the Cisco 3660 chassis. (See Figure
Note Connect the alarm terminal block to either an AC power source rated maximum 25 VAC and 5A current rating, or a DC power source rated maximum 30V and 5A current rating.
Figure
VCC OK |
|
|
SYSTEM |
|
|
FDX | FDX |
|
LINK |
| |
100Mbps | LINK | 1 |
| 100Mbps | |
|
| 0 |
22861
Step 6 Reinstall network cables, and turn ON power to the router.
NEBS Level 3 and ETSI Compliance Kit Installation Guide for Cisco 3620, Cisco 3640, and Cisco 3660 Routers
| ||
|