. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Planning Installation
Writer: Chris Seiter Project: Planning Installation Comments: 299440-001
File Name:2824_2.DOC Last Saved On:6/27/97 3:51 PM
CAUTION: The power outlet must be a non-switched, three-pronged,
grounded outlet. Do not use a three-to-two pronged adapter at the outlet.
Doing so may result in electrical shock and/or damage to the hub and will
void your warranty.
Spatial RequirementsThe hub dimensions are 2.5 x 17 x 13.5 inches, 6.4 x 43.6 x 34.6 cm (HxWxD).
Be sure to allow at least 2 inches (5.1 centimeters) on each side of the hub for
proper air circulation and cable connections.
Cable RequirementsThe following information states the required cable type and distance
limitations for 10Base-T, 100Base-TX, and 100Base-FX.
10Base-T
The 10Base-T twisted-pair wiring you connect to the hub’s RJ-45 ports must
meet the following minimum specifications and requirements to ensure long-
term LAN reliability.
■ The wiring must be unshielded twisted-pair (UTP), Category 3 or better.
■ Two pairs of wiring are required.
■ The building codes may require different insulation materials.
■ The wire gauge should be between 18 and 26 AWG. (Most telephone
installations use 24-gauge wiring.)
■ UTP wire should meet the following requirements:
Solid copper
Nominal capacitance: less than 16 pF/ft
Nominal impedance: 100 Ohms
Nominal attenuation: less than 11.5 db