2.3DRAIN CONNECTION:
A.The unit is supplied as standard with a ProCon type pump. In some cases, it may be necessary to drain the unit. This is done by removing the pump volute plug in the pump assembly.
B.Note that if chemical treatment of process fluid or additives are use, drainage shall be done according to local codes.
C.It is important to note that drainage procedures must be done prior to shipment or outdoor storage or the unit. If not, freezing damage can occur.
Motor
Thermocouple
Pump
Drain plug
2.4AIR COOLED CONDENSER
A.
B.Air flow is generated by the motor driven fan. Air flow is from the outside of the chiller, through the condenser and exhausted through the unit. Exhaust air can not be ducted on motor driven fan models.
C.A free air space of at least four (4) feet is required at the condenser intake and four (4) feet at the condenser discharge to allow for proper air flow.
D.At full load, this chiller will discharge approximately 15,000 BTU/hr per hour per ton of cooling.