°F CAPACITY

8.5CHILLER CAPACITY AND DERATE CHART

Standard chiller rating is at 50°F. For all other temperature settings,

output tonnage is altered as follows:

OUTPUT FULL TEMPERATURE AVAILABLE %

°F CAPACITY

60105%

50100%

4590%

4080%

3570%

3060%

2550%

2040%

15

30%

*

10

22%

*

5

15%

*

0

9%

*

-5

5%

*

NOTES:

If operation of the chiller at less than 48°F is required, an inhibited propylene glycol solution is required.

Consult factory for chiller operation below 20°F.

Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at 95°F entering air temperature. For ambient air conditions greater than 95°F, chiller derating will occur. For ambient temperatures of 95-105°F, select the next larger capacity chiller. For ambient temperatures over 105°F, consult factory.

*These ranges require special options.

UGH020/0301

VL Series Portable Chillers, 0.25 to 1.5 Tons