Cooline PT036 Unit Weight & Weight Distribution, Condensate Drain Connection, Duct Connection

Models: PT360 PT036

1 31
Download 31 pages 52.58 Kb
Page 7
Image 7

CONDENSATE DRAIN CONNECTION

Use standard PVC pipe with NPT connection for the condensate drain. Provide a 'P' trap immediately at the condensate drain connection. Piping has to be sloped away from the unit.

Remember to remove the drain hole plug before operating the unit. Avoid bends & elbows.

DUCT CONNECTION

The units can be connected to the ducting in horizontal configuration. Connect ducting using flexible duct connection. The duct should be properly designed and the drive package should match the required CFM & corresponding external static pressure.

ATTENTION: Avoid abrupt changes in size and/or direction of duct to ensure proper unit performance.

ELECTRIC HEATERS

Electric heater kit is installed in the unit at the supply air opening space.

UNIT WEIGHT & WEIGHT DISTRIBUTION

MODEL

 

 

WEIGHTS (Kg.)

 

 

 

 

 

 

 

 

NUMBER

J

K

M

L

P

Q

 

PT036

67

36

51

34

-

-

 

 

 

 

 

 

 

PT048

72

41

57

39

-

-

 

 

 

 

 

 

 

PT060

76

45

62

42

-

-

PT075

86

52

70

45

-

-

 

 

 

 

 

 

 

PT090

116

92

95

73

-

-

 

 

 

 

 

 

 

PT100

134

91

98

73

-

-

PT120

135

91

98

73

-

-

 

 

 

 

 

 

 

PT180

155

99

152

85

108

105

 

 

 

 

 

 

 

PT215

182

89

94

101

177

103

PT240

186

94

98

105

181

107

 

 

 

 

 

 

 

PT300

226

130

202

148

221

158

 

 

 

 

 

 

 

PT360

256

145

216

151

249

175

 

 

 

 

 

 

 

J

 

P

CONDENSER SECTION

M

 

Q

= =

SUPPLY AIR/

RETURN AIR

K

L

6

Page 7
Image 7
Cooline PT036, PT360 Unit Weight & Weight Distribution, Condensate Drain Connection, Duct Connection, Electric Heaters