DOCUMENT 1025

REV. B

Instruction Manual

 

 

 

 

 

AGS-LED

 

 

 

 

 

858 LED Series

 

 

 

 

 

Sizes 1, 2, 3, 4 and 5

 

 

 

 

 

 

9

Installation

 

 

 

 

 

 

 

WARNING:

 

 

 

 

 

 

NOTICE

Sign foundaations/pad and their design are the responsibiility of the

 

 

 

 

installer and/or airport and recommendations/suggestionns herein are

for guidance only. Transformer housing and baseplates and/or covers, seriees isolation transformers, primary connector kits, series isolation traansformer secondary cable extender, series isolation consolidatinng harness (if required), heat shrink kits, grouunding rods, ground wire and connectors, floor flange anchor bolts annd hardware are not included as part of the sign. Underlined items may be ordered from Crousse-Hinds Airport Lighting.

a.Refer to FAA AC 150-5345-18F section 14 for Taxiway Guidance Sign location and for the perpendicular distance from the defined pavement edge to the near side of the sign. Similarly, see section 25 of FAA AC 150-5345-18F for Runway Distance Remaining Sign locatio n and perpendicular distance from the defined pavement edge to the near side of the sign.

WARNING:

IMPORTANT FAA specifiications and Engineering Briefs may be obtained by searching thhe FAA web site: www.faa.gov.

b.See Figures 12-17 for suggested concrete foundation/pad. Concrete foundations/paads should be of adequate mass, reinforcement, and psi strength rating for the maximum sustained foorce on the sign body and floor flange anchors must endure at its maximum plus a safety margin. The concrete foundation/pad should be installed in soil conditions that will help facilitate drainage and foundation/pad support. The flooor flange anchor bolt material should also meet the maximum sustained force on the sign bodyy plus a safety margin and must be ½ inch in diamet er for use with the 25684-1 Floor Flange. See Tabble 14 for estimated maximum sustained force on the sign body.

c.Concrete foundations/pads shouuld extend at least 12 inches below the local frost line. Contact your local or regional building inspecctor if the depth is unknown for your area. The founndation/pad should extend at least 1 foot beyond the sign body to minimize damage from mowers.