(800) | INSTALLATION INSTRUCTIONS | |
www.cooperwheelock.com | SERIES RSSWP STROBE WEATHERPROOF APPLIANCE | |
|
| (WALL/CEILING MOUNT VERSION) |
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Series RSSWP Strobes can provide a
NOTE: Final acceptance is subject to authorities having jurisdiction (AHJ).
NOTE: All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems,
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CAUTION: NOT RECOMMENDED FOR USE AT REFRIGERATOR / FREEZER DOOR ENTRANCES OR OTHER AREAS WITH PERSISTENT CONDENSATION.
SPECIFICATIONS:
Table 1: UL/ULC Models and Ratings
| Regulated | Strobe Rated | Voltage Range | ULC Rated | UL Rated Strobe Candela | Maximum | Maximum | ||
| Per | Strobe |
| (cd) | |||||
Model | Voltage | Voltage | CAN/ULC- | Candela | At |
|
| RMS Current | RMS Current |
| (VDC/VRMS) | (VDC/VRMS) | (cd) | (UL1638) |
| (UL1971) | Draw (DC) | Draw (FWR) | |
|
|
| (VDC/VRMS) |
|
|
|
|
|
|
24 | 30 | 115 |
| 30/180 * | 0.138 | 0.222 | |||
24 | ~ | ~ | 115 |
| 30/180 * | 0.138 | 0.222 | ||
24 | ~ | ~ | 50/75 |
| 115/177 | 0.300/0.420 | 0.455/0.645 | ||
24 | ~ | ~ | 65/90 |
| 135/185 | 0.300/0.420 | 0.455/0.645 |
*180cd is on Axis only.
NOTES:
1.Strobes will produce 1 flash per second over the “Regulated Voltage” range.
2.Strobes with clear lens meet the required light distribution patterns defined in ULC
3.All models are listed for indoor and outdoor use. UL 1971 is tested from a temperature range of 32ºF to 120ºF (0ºC to 49ºC). UL 1638 is tested from a temperature range of
4.Candela ratings listed in Table 1 are for clear lens. Derate 70% for blue (B), 25% for amber (A), 55% for green (G), and 80% for red (R) lens
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF A PRODUCT.
When calculating the total currents use Table 1 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as “Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
Copyright 2007 Cooper Wheelock All rights reserved. | P84824 D |