![DO NOT VENT REFRIGERANT TO ATMOSPHERE](/images/new-backgrounds/73345/733459x1.webp)
WARNING: To avoid eye injury, wear protective glasses or goggles while working with refrigerant or brazing.
DO NOT VENT REFRIGERANT TO ATMOSPHERE
NOTE: Work in a
1.Remove refrigerant from the unit as follows:
2.At the compressor, install a tap line in the suction process line.
3.At the dual inlet drier, install a second tap line valve on the discharge process line.
4.Connect the tap line valves to the refrigerant recovery system and draw off the refrigerant.
KIT INSTALLATION
1.Very carefully (see Figure 1), bend COPPER EVAPORATOR COIL (item 4) long tube from shipping posi- tion to installation position. BE VERY CAREFUL DURING BENDING NOT TO KINK TUBE.
2.Install COIL SPACERS (item 5) on COPPER EVAPORATOR COIL (item 4).
3.Very carefully, install copper evaporator coil assembly in evaporator tank with coil inlet and outlet tubes positioned in corner where front and side panels are separated.
4.Cut old evaporator coil refrigeration tubes off
5.Remove old suction line assembly, including accumulator and old
6.Very carefully (see Figure 1) bend SUCTION LINE ASS’Y (item 1) from shipping position to installation position. BE VERY CAREFUL DURING BENDING NOT TO KINK TUBE.
7.Place new SUCTION LINE ASS’Y (item 1) in position inside unit. Larger suction line and capillary tube to be routed from lower part of unit up through opened corner to inside of evaporator tank.
8.Place large suction line inside line leading up from bottom of copper evaporator coil. Place capillary tube in line leading from top side of evaporator coil.
9.Using proper soldering procedure, solder copper evaporator coil tube connections.
CAUTION: STRAINER DRYER, DUAL INLET (item 8) must be installed in horizontal position to avoid premature compressor failure.
NOTE
NOTE
WARNING: To avoid possible personal injury, do not apply heat to a charged system.
10.Connect ‘‘dry’’ nitrogen
5 | 189159001 |