GENERAL INFORMATION
INTRODUCTION
The REMCOR ”CH” Series Recirculating Water Chiller is designed to provide an accurate, reliable, and user– friendly system for cooling a continuous flow of water and keep it at a constant temperature in various closed loop or tank cooling applications.
The ”CH” Series Chiller consists of an
The ”CH” Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the ”CH” Series Chiller will provide years of trouble free service.
UNPACKING AND INSPECTION
This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Re- quest a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event that an immediate replacement is necessary, please contact REMCOR Chiller Sales at
DESIGN DATA
| Table 1. Design Data |
|
|
|
|
| CH250 | CH251 |
Cooling Capacity: |
|
|
BTU/hr (W) at 80_ F(27_ C) and | 3,000 (879) | 3,000 (879) |
70_ F (21_ C) Liquid Temperature. |
|
|
|
|
|
Compressor Horsepower | .25 (.2 kW) | .25 (.2 kW) |
|
|
|
Electrical Data: | 115/1/60 | 230/1/60 |
Voltage/Phase/Hertz/Amperage | 7.5 Amps | 3.8 Amps |
|
|
|
Refrigerant Type: | R134a | R134a |
|
|
|
Physical Dimensions, Width X Depth | 17.125” X 14.125” X 13.375” | 17.125” X 14.125” X 13.375” |
X Height | (43.5 cm X 35.9 cm X 34cm) | (43.5 cm X 35.9 cm X 34cm |
Fittings: |
|
|
Process Connections | 1/2” FPT (S/S) | 1/2I FPT (S/S) |
Optimum Process Liquid Flow GPM | 0.6 (2.72) | 0.6 (2.72) |
(Liters/Min) |
|
|
Condenser Air Flow (CFM) | 225 | 225 |
DATA PLATE INFORMATION
MADE IN U.S.A.
REMCOR PRODUCTS COMPANY
GLENDALE HEIGHTS, IL. |
|
|
|
|
|
|
| |
PART NO. |
| MODEL NO. |
|
| SERIAL NO. | |||
VOLTS | HZ |
|
| PH |
| AMPS |
| R134A |
BAR CODE
FIGURE 1. SAMPLE DATA PLATE
1 | 620914801 |