FLUID RECOMMENDATION

Remcor Chillers are designed to operate with water to provide maximum performance for temperatures of 40_F–100_F.

Distilled Water

De–Ionized Water (1–5 MEG/OHMS)

De–Ionized Water (5+MEG/OHMS)

Propylene Glycol

(Lab & Industrial Grade)

Lab & Industrial Grade Ethylene Glycol

Mineral/Hydraulic Oils

(Viscosity<50 Centistrokes)

Ethylene Glycol

(Commercial/Automotive Antifreeze)

Acceptable

Acceptable

Acceptable with Stainless Steel & PVC only

*No Copper or Brass

Acceptable – 30% Glycol/70% Water

*For Applications with Temperatures below 40_F

Acceptable – 30% Glycol/70% Water

*For Applications with Temperatures below 40_F

Acceptable

NOT Acceptable

*Silicate Rust Inhibitors in Automotive/Commer- cial Antifreeze will damage pump seals and housing which lead to failure.

Acidic/Basic Solutions

Not Acceptable

(Above 8/Below 6 PH)

 

Mineral/Hydraulic Oils

Not Acceptable

(Viscosity>50 Centistrokes)

 

For questions regarding special or other fluids contact IMI Cornelius Remcor at 800–551–4423.

To Purchase Lab or Industrial Glycol contact:

Hubbard Hall

(800)

648–3412

– Dow Therm SR1 available in 5 gallon

IMI Cornelius

(800)

551–4423

– Part# 111521000 5 gallons

5

620914801

Page 7
Image 7
Cornelius CH 250, CH 251 manual Lab & Industrial Grade Ethylene Glycol, Commercial/Automotive Antifreeze