FLUID RECOMMENDATION
Remcor Chillers are designed to operate with water to provide maximum performance for temperatures of
Distilled Water
Propylene Glycol
(Lab & Industrial Grade)
Lab & Industrial Grade Ethylene Glycol
Mineral/Hydraulic Oils
(Viscosity<50 Centistrokes)
Ethylene Glycol
(Commercial/Automotive Antifreeze)
Acceptable
Acceptable
Acceptable with Stainless Steel & PVC only
*No Copper or Brass
Acceptable – 30% Glycol/70% Water
*For Applications with Temperatures below 40_F
Acceptable – 30% Glycol/70% Water
*For Applications with Temperatures below 40_F
Acceptable
NOT Acceptable
*Silicate Rust Inhibitors in Automotive/Commer- cial Antifreeze will damage pump seals and housing which lead to failure.
Acidic/Basic Solutions | Not Acceptable |
(Above 8/Below 6 PH) |
|
Mineral/Hydraulic Oils | Not Acceptable |
(Viscosity>50 Centistrokes) |
|
For questions regarding special or other fluids contact IMI Cornelius Remcor at
To Purchase Lab or Industrial Glycol contact:
Hubbard Hall | (800) | – Dow Therm SR1 available in 5 gallon | |
IMI Cornelius | (800) | – Part# 111521000 5 gallons |
5 | 620914801 |