Cornelius MJ31-4 PB, MJ32-4 PB Cont, Troubleshooting Guide, Problem, Probable Cause, Remedy

Models: MJ31-4 PC MJ31-4 PB MJ30-4 PC MJ30-4 PB MJ32-4 PC MJ32-4 PB

1 59
Download 59 pages 14.54 Kb
Page 16
Image 16

Troubleshooting Guide

Problem

Probable Cause

Remedy

TWO OR MORE PUMPS

VRB Board mounting screw

Check the corresponding VRB board

OPERATE WHEN ONLY

insulator is missing or

to the valve that is dispensing in

ONE BUTTON IS PUSHED.

improperly installed.

error. Where the screw mounts the

(Cont.)

 

transistor to the bracket, be sure that

 

 

the spacer bushing is present and the

 

 

screw is not over tightened. Screw

 

 

contact with the bracket will cause a

 

 

short and the firing of the valve when

 

 

other valves are energized.

WITH POWER PRESENT

Refrigeration shut off switch

Refrigeration shut off switch is

DISPENSER WILL NOT

is in the off position.

located on the top of the dispenser.

COOL

 

This switch will disable the

 

 

compressor and condenser fan motor.

 

 

Be sure the switch is in the on

 

 

position.

Drink temperature should be

Depleted ice bank (not

Remove rear bonnet covering the

35-45°F

applicable after period of

refrigeration deck. CAUTION should

°

heavy usage.)

be observed when working in this

2-7 C

 

area as the dispenser is energized and

 

 

 

 

operational. Check to see if the

 

 

compressor is running . If so allow

 

 

the system to recover (approximately

 

 

1 hour).

WITH POWER PRESENT

Loose or broken wire

Check the wire connections at the

COMPRESSOR WILL NOT

connections.

compressor. Be sure they are tightly

RUN.

 

secured.

(Compressor shell is cold to

 

 

touch.)

Defective compressor start

Check the compressor start relay.

 

component.

Replace as required.

 

Ice bank control not connected

Check the ice bank control

 

or defective.

connections. To test, place jumper

 

 

between the 2 leads. If the

 

 

compressor starts ,the ice bank

 

 

control is defective.

COMPRESSOR RUNS BUT

Low refrigerant charge.

Contact a refrigeration service

NO COOLING IS TAKING

 

technician. They will check for leaks

PLACE.

 

(sign of oil at joints and fitting) and

 

 

will recharge if necessary.

 

Refrigerant restriction.

Refrigeration technician will examine

 

 

the system for, kinks in lines,

 

 

restrictions, etc. Heat exchanger may

 

 

need to be replaced.

 

 

 

15

Page 16
Image 16
Cornelius MJ31-4 PB, MJ32-4 PB, MJ32-4 PC, MJ30-4 PB, MJ30-4 PC Cont, Troubleshooting Guide, Problem, Probable Cause, Remedy